<100kVA Range
LQLVF-54KVA/2*135A Power Noise Filter: High-Density EMI Suppression for Electrical Distribution Systems
Core Technical Specifications
Parameter | Specification |
---|---|
Model | LQLVF-54KVA/2*135A |
Rated Voltage | 0.4kV Input/Output |
Rated Current | 135A per Circuit (270A total) |
Frequency | 50-60Hz |
Circuits | 2 Independent Channels |
Full-Load Operation | 60 minutes at 100% rating |
Insulation Level | 3kV for 1 minute |
Installation | Sub-stage Switchgear Cabinet |
Weight | 30kg (Approx.) |
Performance Specifications
Attenuation:
40kHz-100kHz: >40dB
100kHz-1MHz: >60dB
Filter Reactor Q-Factor: >70 (Low signal distortion)
Partial Discharge: <3pC (Precision noise control)
Insertion Loss: <0.35dB at 50Hz
Frequency Range: 50-60Hz operation
Switchgear Cabinet Integration
Space-Optimized Design: Direct mounting in standard sub-stage switchgear compartments
High-Density Construction: 1.8kVA/kg power density
Thermal Management: Natural convection cooling compatible with cabinet airflow
EMI Containment: Shielded enclosure prevents noise propagation
Vibration Resistance: Designed for switchgear environments
Dual-Circuit Design Advantages
Independent Noise Control: Separate EMI filtering for different distribution branches
Cross-Talk Prevention: -75dB inter-circuit interference rejection
Load Balancing: 135A per circuit for precise power distribution
Maintenance Redundancy: Service one circuit while maintaining partial operation
Industrial Applications
Electrical substation control panels
Industrial power distribution cabinets
Manufacturing plant motor control centers
Data center power distribution units
Renewable energy converter stations
"Dual-circuit EMI filters with <3pC PD levels are essential for modern switchgear where electromagnetic interference can compromise protective relaying and metering accuracy."
– IEEE Transactions on Power Delivery
Switchgear Installation Guidelines
Mount on dedicated mounting plate in switchgear compartment
Maintain 60mm clearance from protective relays and meters
Use 40mm² minimum copper conductors with compression lugs
Implement cabinet grounding with <0.05Ω resistance
Verify circuit isolation before energization
Align with cabinet ventilation paths
Performance Validation Tests
Test | Standard | Result |
---|---|---|
Temperature Rise | IEC 62271-1 | 62°C at full load |
Partial Discharge | IEC 60270 | <3pC at 1.5Ur |
Dielectric Strength | IEC 60060-1 | 3kV/1min pass |
Switchgear Compatibility | IEC 61439-1 | Form 4a separation compliant |
Compliance & Standards
IEC 61000-6-5 (Power station emissions)
IEC 62271-200 (AC metal-enclosed switchgear)
ANSI/IEEE C37.20.2 (Medium-voltage switchgear)
EN 50522 (Earthing of power installations)
Maintenance Protocol
Interval | Action | Acceptance Criteria |
---|---|---|
Monthly | Infrared thermography | ΔT ≤ 35°C from ambient |
Quarterly | Connection torque check | 45N·m ±5% |
Biannual | Insulation resistance | >500MΩ at 2.5kV DC |
Annual | Attenuation verification | ±3dB of initial specification |
Safety Considerations
De-energize switchgear compartment before installation/service
Verify discharge of capacitive elements (5τ time constant)
Use CAT III/IV PPE per NFPA 70E
Follow LOTO procedures during maintenance