LQHV-625 SF6 Gas Recovery Device: Complete Gas Management Solution
Professional-grade equipment for efficient recovery and purification of sulfur hexafluoride (SF6) gas from high-voltage electrical equipment. Complies with DL/T 506-2018 industry standards.
Product Parameter
Technical Parameters
Recovery | Initial recovery pressure ≤0.8MPa |
Final recovery pressure ≤50KPa | |
Recovery time: For 1 m3 SF6 gas volume with initial pressure of 0.8MPa, recovery to the final pressure of 50KPa, the recovery time is less than 2.5 hours | |
Aeration | 1 m3 SF6 gas volume with initial pressure of 133Pa is charged to 0.8mpa, and the charging time is less than 0.8 hours |
Vacuum extraction | The limit vacuum degree of the device is less than or equal to 10 Pa, and the time required to vacuum the 1 m3 SF6 gas volume with an initial pressure of 0.1MPa to 133Pa is less than 1.0 hours |
Storage | Storage container volume 0.05m3 |
Nominal liquid storage capacity 50kg | |
Maximum storage pressure 3.8MPa | |
Decontamination | For SF6 gas with water content below 1000PPM (volume ratio), after recovery and purification by the device, the water content is less than 60PPM (weight ratio), and the oil content is less than 10PPM (weight ratio). |
Annual leakage rate | ≤1% nominal storage |
Noise | ≤75dB(A) Sound pressure level |
Operating ambient temperature | -10℃-40 ℃ |
Power source | AC three-phase five-wire system 50Hz 400V±10% |
Power | ≤5kW |
Weight | About 545kg |
Overall dimensions (L × W × H) | 1450×810×1200mm3 |
Main component performance parameters
Index name | SF6 Gas Recovery Device |
Power supply AC | 380(three five-wire, phase sequence automatic conversion) |
Rated maximum gas storage pressure (20℃) | ≤4MPa |
Limiting vacuum | ≤10Pa |
Device vacuum maintenance | At 133Pa pressure for 24H, the vacuum value rose < 400Pa |
SF6 Compressor | French Meyoule |
Compressor pumping rate | 7m3/h (customizable) |
Vacuum pump | 2X-4 |
Vacuum pump pumping rate | 15m3/h |
Recovery device ADAPTS to inlet initial pressure (20℃) | 0-1.0 MPa |
Final pressure of electrical equipment recovery (20℃) | ≤50Kpa |
Gas oil control after recovery | Domestic oil content < 10μg/g |
Unit annual air leakage rate | < 1% |
Continuous trouble-free operation time of the device | ≥1000h |
Cumulative trouble-free running time | ≥5000h |
Noise level | Machine ≤75dB(A) |
Theoretical liquid storage capacity | 50kg |
Refrigerated liquefaction compressor | Dombe |
Refrigerated storage tank | 50L |
Recovered gas moisture | 60PPM/V |
After recovery of gas oil | 10PPM/V |
Dry filtration system | Vacuum heating activation regeneration |
Initial gas pressure | ≤133pa |
Charging final pressure | 0.8 mpa |
Inflation rate | ≥5m3/h |
Gasification mode | Electric heating automatic temperature control |
Vehicle type | push-type |
Overall dimension | 1450×810×1200cm3 |
Machine weight | About 545kg |
Cooling mode | Air cooling |
Filtration system | The use of American HASON technology, three-stage filtration - can higher remove the recovered SF6 gas in the water, oil, particulate impurities and dust, to ensure that the recovered SF6 gas reuse |
Concise parameter table
Model number | SF6 Gas Recovery Device |
Vacuum pump pumping speed | 15m3/h |
Limiting vacuum | 10Pa |
Vacuum pump | Domestic bipolar vacuum pump |
SF6 Recovery compressor | 7m3/h |
Stress | 2.5 MPa |
Compressor manufacturer | French Meyoule |
Filter particle | 0.02 micron |
Oil content | High Efficiency (PPM) |
Acid number | 0.1 parts per million |
Hydrolyzable fluoride | 0.2 parts per million |
Biotoxicity | no |
Moisture | ≤60PPM |
SF6 purity | 99.9% or higher |
SF6 storage tank | 50L |
SF6 tank material | Carbon steel |
Refrigeration system | High quality and efficient compressor |
Filter | American original |
Dryer | American original |
Vacuum gauge | pointer |
Valve | Unique technology (built-in butterfly seal to ensure that multiple switches do not leak) |
Advanced System Features
1. Intelligent Protection System
Phase sequence protector prevents motor reversal
Automatic temperature control (-20°C operation capability)
Overload and short-circuit protection
2. Maintenance-Free Design
Built-in regeneration system for desiccant reactivation
Self-cleaning particulate filters
Oil-free compression system
3. Ergonomic Mobility
High-grade casters with floor protection
Compact footprint (1200×800×1100mm)
Integrated control panel
Working Principle
The LQHV-625 performs gas recovery through a four-stage process:
Extraction: Withdraws SF6 gas from equipment via compressor
Liquefaction: Cools gas to liquid state for storage
Purification: Multi-stage filtration removes:
Moisture (dew point ≤ -60°C)
Decomposition byproducts (SO2, HF)
Particulate contaminants
Recharging: Returns purified gas to equipment
Industry Compliance
Meets critical standards for SF6 gas handling:
DL/T 506-2018 (SF6 Gas Recycling Device Technical Specifications)
IEC 60480 (Guidelines for SF6 reuse)
GB/T 8905 (SF6 Gas Handling Regulations)
Why Choose LQHV-625?
Cost Savings: Recycles up to 95% of SF6 gas (market value $20-$50/kg)
Environmental Safety: Prevents greenhouse gas emissions (SF6 GWP=23,900)
Maintenance Efficiency: 30% faster recovery than conventional units
Operator Protection: Fully enclosed gas path prevents exposure
Contact our technical team for customized SF6 gas management solutions for your substation or manufacturing facility.