Product Parameters

Main technical parameters

Capacity measuring range30kVA ~ 31500kVA
Current measuring range0 -100A  auto-switch the measurement range
Current measurement accuracy± (0.2% + 3digits)
Voltage measurement rangeLine Voltage0-750V;phase voltage 0-450V, auto-switch the measurement range
Voltage measurement accuracy± (0.2% + 3digits)
Insulation resistance> 100MΩ
Leakage current<3.5mA
Dielectric strengththe power connection on the chassis can withstand: 1500V External transformer can broaden the scope of measurement instruments
Frequency Range40 ~ 65Hz, accuracy class 0.2;
Power InputAC220V ± 10%
  • Transformer capacity (up to 2500kVA)

  • No-load current and losses

  • Short-circuit voltage and load losses

  • Power quality harmonics (up to 50th order)

Advanced Testing Technology

1. Intelligent Three-Phase Analysis

  • 🔌 Auto-wiring verification with vector diagrams

  • ⚡ Simultaneous voltage/current waveform capture

2. Automatic Correction Systems

  • 🌡️ Temperature compensation (20°C reference)

  • 📈 Waveform distortion adjustment

  • ⚙️ Non-rated voltage/current conversion

3. Extended Measurement Capability

  • 🔗 External CT/PT connections for large units

  • 📊 1/3 current loading tests for 2500kVA transformers

Field-Optimized Features

  • All-Weather Operation: -10°C to 50°C range

  • Data Integrity: Flash memory with timestamp

  • Reporting: Onsite thermal printing

  • Connectivity: USB data export

Typical Applications

  • Utility Companies: Distribution transformer evaluation

  • Manufacturers: Factory acceptance testing

  • Service Teams: Loss assessment after faults

  • Energy Audits: Efficiency benchmarking

Why Choose LQHV-321?

  • Complete Testing: Capacity + losses in one unit

  • Smart Corrections: 5 automatic adjustment systems

  • Field Expandable: Works with external CTs/PTs

  • Data-Rich: Harmonic analysis + vector diagrams

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message