Transformer Testing Instrument
LQHV-3000 On-Load Tap-Changer Tester
Comprehensive OLTC Performance Analysis
The LQHV-3000 delivers precise diagnostics for transformer tap-changers with dual-current output and automatic transition calculations, essential for:
Preventive maintenance programs
Post-fault switchgear evaluation
Factory acceptance testing
Product Parameters
Technical parameters
The output current | 1.0A、0.5A | |
Measuring range | Transition resistance | 0.5Ω~20Ω(1.0A)、0.5Ω~40Ω(0.5A) |
Transition time | 0~250ms | |
Accuracy of measurement | Transition resistance | ±(5% reading +3 words) |
Transition time | ±(0.1% reading +3 characters) | |
The environment temperature | -10℃~50℃ | |
Environmental humidity | ≤85%RH | |
Working power supply | AC220V±10% | |
Power frequency | 50±1Hz | |
storage | U disk storage, local storage | |
Overall dimensions | 345mm×295mm×175mm | |
Instrument weight | 5kg |
Advanced Testing Technology
1. Dual-Current Analysis
🔌 1A precision mode for sensitive detection
⚡ 10A power mode for noisy environments
📈 Auto-range selection
2. Intelligent Waveform Processing
⏱️ Automatic transition time calculation
📊 Resistance curve differentiation
🔄 Three-phase synchronism analysis
3. Field-Optimized Operation
🖥️ One-key shuttle control
💾 USB waveform storage (100+ tests)
🛡️ Live circuit protection
Critical Measurements
Contact Wear: Transition resistance values
Mechanical Timing: Switch transition duration
Phase Alignment: Three-phase synchronization
Arcing Detection: Waveform anomalies
User-Centric Features
All-in-One Display: Waveform + digital results
Portable Design: 5kg field-ready package
Data Export: PC analysis software included
Safety Systems: Automatic discharge
Why Choose LQHV-3000?
✅ Dual-Current Advantage - Wider measurement range
✅ Smart Calculations - Auto resistance/time values
✅ Visual Diagnostics - Waveform comparison
✅ Regulatory Ready - Meets IEC 60214-2