800kV ~ 1600kV Range
LQHIVG 1400KV-140KJ Impulse Voltage Generator: Ultra-High Voltage Testing Solution
Product Overview
The LQHIVG 1400KV-140KJ Impulse Voltage Generator represents the pinnacle of high-voltage testing technology with its industry-leading 1400kV rating and 140kJ energy capacity. Featuring a robust 7-stage design with 20kJ per stage, this IEC 60060-compliant solution delivers precision lightning impulse (±3%) and switching impulse performance across an exceptional 400-3400pF load range. Engineered for critical applications in power transmission research, electrical infrastructure validation, and specialized testing facilities.
Compliance with International Standards
IEC 60060-1/2-2010: High-voltage test definitions and measurement protocols
IEC 61083-1/2: Instrumentation for impulse tests
ANSI/IEEE 4a-2001 & 1122-2007: Testing techniques and digital recording
ASTM D69/D2518: Electrical insulation standards
GB311/GB16927: Waveform compliance certification
Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | ±1400kV |
Rated Energy | 140kJ |
Stages | 7 |
Stage Voltage | 200kV |
Stage Capacitance | 1.0µF |
Stage Energy | 20kJ |
Load Range | 400-3400pF (includes divider) |
Voltage Stability | <±1.0% |
Waveform Performance
Lightning Impulse Full-Wave
Waveform: 1.2±30%μs / 50±20%μs
Peak Tolerance: ±3%
Peak Oscillation: <5%
Minimum Efficiency: ≥90% (no load)
Switching Impulse Wave
Waveform: 250±20%μs / 2500±60%μs
Efficiency: ≥70% (1000pF load)
Compliance: Meets GB16927 requirements
Operational Features
Exceptional Load Tolerance: 400-3400pF range (including divider)
Precision Synchronization:
Voltage range: 10%-100% rated
Polarity deviation: <20%
Discharge failure rate: <2%
Advanced Cycling:
120s cycle (>70% voltage)
60s cycle (<70% voltage)
Robust Capacitor Design: 1.0µF/200kV modules per stage
Voltage Stability: <±1.0% charging instability
Industrial Applications
Ultra-high-voltage transmission research
Next-generation transformer testing
Power grid substation equipment validation
High-voltage circuit breaker certification
National research facility applications
Renewable energy infrastructure testing
Advanced insulation material research
Technical Advantages
Industry-Leading Voltage Rating: 1400kV capacity for cutting-edge research
High-Energy Density: 140kJ total with 20kJ per stage
Exceptional Load Flexibility: 400-3400pF range accommodates diverse test setups
Research-Grade Efficiency: ≥90% voltage utilization for lightning tests
Robust 7-Stage Design: Ensures stability at extreme voltages
Precision Waveform Control: ±3% tolerance meets GB16927 requirements
Rapid Cycling Capability: 60-120s operational cycles