100kVA ~ 150kVA Range
LQDZ 125kVA |380V Input | 0-3.3kV Adjustable Output |Manual Contact Voltage Regulator| Industrial Voltage Stabilizer
Engineered for Precision High-Voltage Control
The LQCZ-125kVA cylinder-type voltage regulator delivers stable 0-3.3kV adjustable output for demanding industrial applications. Featuring ONAN (Oil Natural Air Natural) cooling and electrical drive regulation, it meets rigorous standards for high-voltage testing, transformer manufacturing, and power quality simulation. With ≤3% waveform distortion and ≤60dB operational noise, it ensures laboratory-grade accuracy in industrial environments.
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 125kVA |
Input Voltage | 0.38kV (380V) |
Output Voltage Range | 0 - 3.3kV (3,300V) |
Input Current | 329A |
Output Current Range | 0 - 38A |
Impedance Voltage | ≤7% (50%-100% regulation range) |
Starting Voltage | ≤1% |
Waveform Distortion | ≤3% THD |
Noise Level | ≤60dB |
Cooling Method | ONAN (Oil Natural Air Natural) |
Core Technologies
1. Intelligent Electrical Drive System
Single-phase DC motor for precise voltage adjustment
Upper/lower limit locks to prevent over-travel faults
Programmable regulating speed with position feedback
2. Robust Overload Protection
Overload Condition | Maximum Duration |
---|---|
120% Rated Current | 60 minutes |
140% Rated Current | 30 minutes |
160% Rated Current | 5 minutes |
3. Short-Circuit Resilience
Withstands >2× output current for 8 AC wave cycles (160ms at 50Hz) without thermal damage or mechanical deformation when used with protective resistors.
Structural Advantages
Cylinder Design: Optimized oil circulation for enhanced heat dissipation
Safety Systems: Oil level indicator, drain valve, and pressure-relief diaphragm
Terminal Protection: Reinforced bushings for 3.3kV output stability

Operational Guidelines
Duty Cycle Management
Standard Operation: 60 mins continuous at 100% rated load
Cooling Recovery: 30 mins idle after maximum duration cycles
Critical Safety Protocols
Verify oil level before operation (min. 25°C)
Engage motor reversal lock during maintenance
Monitor bushings for carbon tracking monthly
Industry Applications
High-Voltage Testing
Dielectric strength validation per IEC 60270
Transformer Manufacturing
Winding stress testing up to 3.3kV
Power Quality Simulation
Voltage sag/swell testing (IEC 61000-4-11)
Compliance & Standards
IEC 60076-1 (Power transformers)
IEEE C57.12.00 (Safety requirements)
EN 50588-1 (Medium power transformers)