LQHCR 750KVA-6KV Oil-Immersed Reactor: 5-Step Capacity & Stepless Regulation
Product Overview
The LQHCR 750KVA-6KV is an advanced oil-immersed compensation reactor featuring 5-step capacity selection and stepless reactance regulation. Designed for 6kV industrial power systems, it provides precise reactive power control with superior thermal management and safety compliance.
Technical Specifications
Parameter | Specification |
---|---|
Model | LQHCR 750KVA-6KV |
Structure | Iron shell, stationary iron core (oil-immersed) |
Rated Capacitance Steps | 5 steps: 150kVar, 300kVar, 450kVar, 600kVar, 750kVar |
Rated Current | 25A, 50A, 75A, 100A, 125A |
Rated Frequency | 50Hz |
Rated Voltage | 6kV |
Phase Configuration | Single phase |
Linearity Degree | < +1% |
Sound Level | < 70dB (measured at 4 meters) |
Temperature Rise | Winding ≤65K, Oil surface ≤55K |
Advanced Engineering Design
Multi-Strand Copper Winding
Parallel-wound copper conductors reduce eddy-current losses with optimized current density ≤2.5A/mm².
Full Insulation System
All terminals withstand 10kV/min ground insulation tests with zero discharge anomalies.
Stepless Regulation System
Single-phase motor-driven iron core enables continuous reactance adjustment without power interruption.
Oil Management System
Moisture absorber maintains dielectric stability
Drain valve for oil sampling/maintenance
Thermal-monitored mineral oil (IEC 60296)
5-Step Capacity Selection
Step | Capacity | Current | Bushing Output |
---|---|---|---|
1 | 150kVar | 25A | Yes |
2 | 300kVar | 50A | Yes |
3 | 450kVar | 75A | Yes |
4 | 600kVar | 100A | Yes |
5 | 750kVar | 125A | Yes |
Manual bushing selection enables rapid capacity adaptation to load demands.
Protection & Safety Systems
Over-Current Capacity
Sustains 120% rated current for 10 minutes without thermal damage or winding distortion.
Over-Voltage Capacity
Handles 110% rated voltage for 10 minutes with no insulation degradation.
Thermal Safeguards
Winding temperature rise limit: 65K
Oil surface temperature rise limit: 55K
Automatic derating above 40°C ambient
Industrial Applications
Cement Plants
Power factor correction for high-torque crusher motors
Petrochemical Facilities
Harmonic suppression in 6kV drive systems
Railway Electrification
Voltage stabilization for traction power substations
Plastic Manufacturing
Reactive power compensation for extrusion line motors
Installation Requirements
Foundation vibration isolation: ≤2.8mm/s (ISO 10816-3)
Minimum clearance: 800mm for ventilation and maintenance
Oil temperature monitoring during commissioning
Grounding resistance: ≤3Ω (IEEE 80)
Maintenance Protocol
Maintenance Task | Frequency | Standard |
---|---|---|
Oil quality analysis | Annually | IEC 60422 |
Winding insulation test | Biannually | IEC 60270 |
Core inspection | Every 5 years | IEEE C57.12.90 |
Moisture absorber replacement | When silica gel >70% saturated | Manufacturer spec |
Compliance Standards
IEC 60076: Power transformers
IEEE C57.18: Reactor standards
EN 50588: Industrial reactor requirements
GB/T 1094.6: Reactor thermal performance