>600kVA Range
LQHCR 1800KVA-10KV Compensation Reactor: Technical Specifications & Industrial Applications
Core Structural Design
Iron-shell construction with stationary iron core, mounted atop test transformers. Engineered for power supply compensation to reduce required power capacity. Features include:
Moisture absorber and oil drain valve for maintenance
Single-phase motor-driven stepless reactance regulation
Bushing terminals for secure output connections
Technical Specifications
Parameter | Value |
---|---|
Rated Capacitance | 300×6kVar (6-step control: 300/600/900/1200/1500/1800kVar) |
Rated Current | 30A / 60A / 90A / 120A / 150A / 180A |
Rated Voltage | 10kV |
Frequency | 50Hz |
Linearity | < +1% deviation |
Acoustic Noise | <70dB at 4m distance |
Safety & Performance Certifications
Robust Overload Protection
Over-current: Withstands 120% rated current for 3 minutes without thermal damage or winding distortion
Overvoltage: Tolerates 105% rated voltage for 10 minutes without insulation failure
Thermal & Insulation Standards
Maximum temperature rise: ≤65K (winding), ≤55K (oil surface)
Full insulation withstand: 42kV/min terminal-to-ground with zero discharge
Industrial Applications
Optimized for high-voltage testing environments requiring precise reactive power compensation:
Transformer testing stations
Power grid harmonic filtration
Renewable energy substations
Dielectric strength validation labs