<1000KV Range
LQHCG 800KV-400pF Multiple Chopping Gap System
Product Overview
The LQHCG 800KV-400pF is a precision-engineered multiple chopping gap system designed for high-voltage impulse testing applications. This 2-stage configuration with 8 pairs of sphere gaps delivers exceptional waveform chopping accuracy with standard deviation below 0.1μs, making it ideal for dielectric testing and power equipment validation.
Key Specifications
Parameter | Specification |
---|---|
Rated Voltage | 800kV DC/Impulse |
Rated Capacitance | 400pF (2×800pF MWF400-800 capacitors) |
Stage Configuration | 2-stage design with 4 sphere gap pairs per stage |
Sphere Gap Type | 8 pairs of 200mm diameter semi-spherical electrodes |
Trigger System | Three-electrode discharge with 10kV/100ns pulse amplifier |
Time Delay | Adjustable 2-5μs with 250kV trigger pulse (GCS2006 compatible) |
Waveform Dispersion | σ < 0.1μs chopping time deviation |
Technical Highlights
Advanced Trigger Mechanism
The three-electrode discharge system utilizes a high-performance pulse amplifier generating 10kV trigger pulses with 100ns rise time, ensuring precise and repeatable gap breakdown.
Precision Time Control
Integrated electric time-delay circuit provides 2-5μs adjustable chopping synchronization, compatible with GCS2006 digital control systems for accurate chopped wave generation.
MWF400-800 Impulse Capacitors
Each stage employs military-grade 800pF capacitors with optimized dielectric construction for minimal energy loss during high-voltage switching operations.
Typical Applications
Lightning impulse voltage tests per IEC 60060-1
Dielectric strength testing of power transformers
Research on insulation breakdown characteristics
Calibration of high-voltage measurement systems
Generator and circuit breaker testing
Operation & Safety Features
Graded Potential Design - Equalized voltage distribution across stages
Anti-flashover Construction - Optimized sphere gap geometry prevents surface tracking
Trigger Isolation - Optically isolated control signals ensure operator safety
Fail-safe Interlocks - Prevents operation unless all safety conditions are met
Compliance Standards
The LQHCG system meets or exceeds:
IEC 60060-1: High-voltage test techniques
IEEE Std 4: Standard for high-voltage testing
EN 61010-1: Safety requirements for electrical equipment
GB/T 16927.1: Chinese national standard for HV testing
Maintenance Requirements
Component | Maintenance Interval |
---|---|
Sphere Gap Cleaning | Every 50 operations or 6 months |
Capacitor Inspection | Annual dielectric strength test |
Trigger Circuit Calibration | Bi-annual verification |
Mechanical Alignment Check | Before critical measurements |