<1000KV Range
LQHCG 300KV-400pF Multiple Chopping Gap: High Precision High Voltage Testing Solution
Product Overview
The LQHCG 300KV-400pF Multiple Chopping Gap is a precision high voltage testing instrument designed for generating controlled chopped waves in high voltage impulse tests. With its 300kV voltage rating and 400pF capacitance, this device provides reliable performance for demanding high voltage testing applications in both industrial and research environments.
Key Features
300kV maximum operating voltage
400pF rated capacitance
Precision timing control (σ<0.1μs)
Four-pair sphere gap configuration
Advanced three-electrode triggering
Detailed Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | 300kV DC/Impulse |
Rated Capacitance | 400pF ±5% |
System Configuration | 1 stage design |
Timing Accuracy | Standard deviation <0.1μs |
Mechanical Configuration
Sphere Gap Quantity: 4 pairs (8 units total)
Gap Type: 150mm diameter semi-sphere gap
Electrode Material: High-conductivity alloy with polished surface
Support Structure: Porcelain or composite insulators
Trigger System Specifications
Trigger Method: Three-electrode discharge trigger
Pulse Amplifier Output: 10kV, 100ns rise time
Time-delay Control: Adjustable digital circuit
Trigger Pulse: 250kV with <5ns jitter
Control Interface: Digital setting of chopping time
Performance Characteristics
Electrical Performance
Voltage withstand: 350kV power frequency, 450kV impulse
Leakage current: <1mA at rated voltage
Partial discharge: <10pC at 300kV
Temperature coefficient: ±0.01%/°C
Timing Performance
Chopping time range: 0.5-20μs (adjustable)
Time-delay resolution: 10ns
Wavefront time: 1.2μs ±20%
Wavetail time: 50μs ±20%
Environmental Specifications
Operating temperature: 0°C to +45°C
Storage temperature: -20°C to +60°C
Relative humidity: <85% non-condensing
Altitude: <2000m (with derating above)
Primary Applications
Transformer Testing
Lightning impulse tests per IEC 60076-3
Chopped wave withstand testing
Insulation coordination studies
High Voltage Equipment Testing
Circuit breaker impulse withstand
Busbar insulation tests
Disconnector switching tests
Research & Development
Dielectric material research
Breakdown phenomena studies
High voltage component development
Operation and Maintenance
Installation Requirements
Minimum clearances: 3m per 100kV
Foundation: Level within ±2mm/m
Grounding: <0.5Ω resistance
Environmental: Clean, dry installation area
Maintenance Schedule
Daily: Visual inspection of electrodes
Monthly: Cleaning of sphere surfaces
Quarterly: Trigger system check
Annual: Comprehensive calibration
Safety Precautions
Always discharge capacitors before servicing
Use HV-rated personal protective equipment
Implement lockout/tagout procedures
Maintain safe working distances
Technical Advantages
Enhanced Precision
The LQHCG 300KV-400pF achieves unprecedented timing accuracy with standard deviation of chopping time less than 0.1μs, meeting the most stringent testing requirements.
Improved Reliability
The four-pair sphere gap configuration ensures consistent performance even under repeated operations, with minimal electrode erosion.
Advanced Control
Digital time-delay control with 10ns resolution allows precise adjustment of chopping time from 0.5μs to 20μs, adaptable to various test requirements.
Conclusion
The LQHCG 300KV-400pF Multiple Chopping Gap represents a significant advancement in high voltage testing technology, combining 300kV rating with 400pF capacitance and sub-microsecond timing accuracy. Its four-pair sphere gap configuration and advanced three-electrode triggering system provide reliable, repeatable performance for transformer testing, high voltage equipment evaluation, and research applications. With proper installation and maintenance, this equipment delivers precise, consistent results that meet international testing standards while ensuring operator safety.