Oil Test Termination
LQCTT-35(B) Slope-Type Oil Test Termination
Advanced test termination for 35kV single-core cables featuring slope-type stress control with insulation oil or Freon TE dielectric medium for high-voltage cable testing applications.
Technical Specifications
Type: Slope Type
Insulation Material: High-quality insulation oil or Freon TE
Semiconductor Strip Length: ~45mm
AC Test Rating: 100kV for 5 minutes
Partial Discharge Test: 95kV with <2pC sensitivity
Cable Compatibility: 35kV single-core cables
Core Diameter: 60mm² (conductor cross-section)
Insulation Cup Dimensions: Ø150mm × 1100mm length
Base Dimensions: 1090×1360mm
Design Features
Slope-Type Stress Control:
Gradual voltage stress distribution
Prevents surface discharge
Dielectric Medium Options:
High-grade insulation oil (mineral-based)
Freon TE (SF6 alternative for HV applications)
Large Insulation Cup:
1100mm length accommodates higher voltages
150mm diameter for proper stress control
Termination Structure:
Robust steel housing with viewing ports
Integrated ground plane
Testing Capabilities
Test Type | Specification | Standard Compliance |
---|---|---|
AC Withstand Test | 100kV for 5 minutes | IEC 60840 |
Partial Discharge Test | 95kV with <2pC sensitivity | IEC 60270 |
Impulse Voltage Test | Compatible with external generators | IEC 60060-1 |
Tan Delta Measurement | Supports dielectric loss testing | IEC 60885 |
Installation & Operation
Preparation Procedure
Strip cable semiconductor layer (~45mm)
Clean and prepare cable end
Fill insulation cup with dielectric medium
Mount cable in termination base
Apply stress control gel at interface
Secure with pressure-tight seals
Dielectric Filling Specifications
Parameter | Insulation Oil | Freon TE |
---|---|---|
Dielectric Strength | ≥45kV/2.5mm | ≥50kV/2.5mm |
Operating Temperature | -20°C to +90°C | -30°C to +100°C |
Replacement Interval | 50 tests or 2 years | 100 tests or 5 years |
Industrial Applications
Factory acceptance testing of 35kV cables
Utility substation cable commissioning
Industrial plant high-voltage maintenance
Cable manufacturer quality assurance
Renewable energy grid connection testing
Research institutions HV cable studies
Safety Features
Pressure Relief System: Automatic venting at 6 atm
Double Grounding: Primary and backup ground connections
Containment Basin: Integrated spill containment
Viewing Ports: Visual monitoring during tests
Interlock System: Prevents access during pressurization
Arc Containment: Designed for internal fault management
Maintenance Protocol
Pre-Test Checks:
Verify dielectric fluid level
Inspect sealing surfaces
Test grounding continuity
After Each Test:
Drain and filter dielectric fluid
Clean cable interface area
Check for fluid contamination
Quarterly Maintenance:
Full dielectric strength test
Pressure relief valve verification
Seal replacement
Annual Certification:
Complete disassembly and inspection
Dielectric fluid replacement
Calibration verification
Compliance Standards
IEC 60840: Power cables with extruded insulation for rated voltages above 30 kV up to 150 kV
IEC 60270: Partial discharge measurements
IEC 60060: High-voltage test techniques
IEEE 400: Guide for field testing of shielded power cables
ISO 9001: Quality management systems
Certified for 35kV cable testing in industrial and utility applications.