High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Partial Discharge Test Equipment

LHVCW Vehicle-Mounted No-PD Test System | Mobile 1000kV GIS/GIL Testing Solution

Mobile testing solution for 1000kV GIS/GIL equipment with ≤3pc discharge. Features hydraulic lifting system and live-line testing capability for field deployments.


  • US$1.00; Negotiated Price
  • Lead time: 90days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LHVCW Vehicle-Mounted No-PD Test System - Mobile 1000kV GIS/GIL Testing

The LHVCW Series brings laboratory-grade precision to field testing with its ≤3pc partial discharge performance and 1000kV capacity - all integrated into a rugged mobile platform for substation deployments.

Product Parameters

Technical parameter

ParametersValue
Voltage level100kV, 200kV, 250kV, 300kV, 500kV, 800kV, 1000kV
Capacity50-2000kVA
The way high voltage is generatedHigh voltage transformer boosting and series resonance (power frequency, frequency conversion), all boosting methods are one-stage boosting without the need for series boosting.
Input voltage (primary voltage)0.35-10kV
Partial discharge capacity of equipment1-3pc under rated voltage (normal environment)
Temperature riseThe temperature rise of the rated current running for 60 minutes shall not exceed 65K (50Hz)

Core Features

Mobile Testing Platform

  • Integrated hydraulic lifting system

  • Road-legal transport configuration

  • 30-minute setup time

Ultra-Low Discharge

  • Fully shielded inflatable chamber

  • ≤3pc guaranteed discharge level

  • SF₆/N₂ gas insulation

Technical Specifications

Voltage ClassUp to 1000kV
Partial Discharge≤3pc (IEC 60270)
Testing ModesAC withstand voltage | PD measurement | Precision testing
MobilityStandard 20ft truck mounting

Field Testing Advantages

  1. Rapid Deployment: Self-contained system requires only external power

  2. Live-Line Capable: On-line installation without shutdown

  3. All-Weather Operation: -30°C to +50°C working range

  4. Reduced Power Demand: 40% lower capacity requirements vs fixed systems

Application Scenarios

GIS Commissioning

On-site acceptance testing for new 500kV+ substations

Emergency Diagnostics

Rapid response to suspected insulation failures

Preventive Maintenance

Scheduled testing for critical transmission assets

System Components

  • Inflatable Test Chamber: 3m³ shielded volume with gas monitoring

  • HV Bushing Interface: For traditional equipment testing

  • Digital Control Console: Touchscreen operation with data logging

  • Protection Systems: Multi-level overvoltage/current safeguards

Compliance Standards

  • IEC 62271-203 (GIS testing)

  • GB/T 11022 (HV switchgear)

  • DL/T 593 (Mobile test equipment)