High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Gas Coupling Capacitor

HGCC-540kV/500pF SF6 Coupling Capacitor - High-Voltage Measurement & Power Line Communication

540kV/500pF SF6 gas-insulated coupling capacitor with 3000:1 ratio and ≤1% accuracy. Features 60-minute continuous operation at 540kV and ≤2pC partial discharge at 432kV.


  • US$1.00; Negotiated Price
  • Lead time: 90days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HGCC-540kV/500pF SF6 Coupling Capacitor - High-Voltage Measurement & Power Line Communication

The HGCC-540kV/500pF SF6 Coupling Capacitor delivers dual functionality for extra-high-voltage (EHV) systems, combining precision voltage measurement (3000:1 ratio, ≤1% accuracy) with 500pF coupling capacity for power line carrier (PLC) communication. Its SF6 gas insulation ensures stable performance across 45-65Hz frequencies.

Technical Specifications

ParameterSpecification
Rated Voltage540kV (594kV withstand for 60s)
Frequency Range45-65Hz (50Hz nominal)
Partial Discharge≤3pC @540kV, ≤2pC @432kV
Continuous Operation60 minutes @100% rated voltage
Voltage Ratio3000:1 ±0.5%

Key Features

1. Dual-Function Design

  • Precision Measurement: ≤+1% accuracy with 3000:1 ratio

  • Signal Coupling: 500pF capacity for PLC systems

  • Wide Frequency Response: 45-65Hz operation range

2. Advanced Insulation System

  • SF6 gas insulation prevents corona discharge

  • Dielectric loss <0.3% at 20°C

  • Temperature coefficient <0.0005/°C

3. Robust Performance

  • 110% overload capability (594kV for 60s)

  • Conducting rod gas capacitor design

  • 60-minute continuous operation at 540kV

Typical Applications

  • EHV Substations: 500kV system voltage measurement

  • HVDC Converter Stations: Valve hall monitoring

  • Power Line Carrier: Protection signaling transmission

  • Research Facilities: Dielectric testing up to 594kV

Standards Compliance

  • IEC 60358-1:2012 (Coupling Capacitors)

  • IEC 61869-1:2007 (Instrument Transformers)

  • IEEE C37.100.1-2007 (Partial Discharge)

  • GB/T 4109-2008 (Chinese EHV Standards)

Operational Guidelines

  • Maximum continuous operation: 60 minutes @540kV

  • SF6 gas pressure range: 0.4-0.6MPa

  • Ambient temperature range: -25°C to +55°C

  • Annual dielectric loss verification recommended

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message