≤100kVA Range
HET 90kVA Variable Frequency Exciter Transformer
High-Frequency High Voltage Solution
This 90kVA exciter transformer features unique wide-frequency operation (20-300Hz) and dual high-voltage outputs, designed for specialized testing applications requiring variable frequency excitation.
Electrical Parameters
Winding | Voltage | Current |
---|---|---|
LV (2x) | 350V | 142.8A |
HV | 1kV / 2.5kV | 40A |
Frequency: 20-300Hz (Rated 22Hz) | Impedance: ≤6% | Output: 30kV/15kV |
Insulation System
LV Winding: 5kV/1min withstand
HV Winding: 50kV/60s withstand
Cylinder winding with turn-to-turn insulation
Electrostatic shield between windings
Compound insulation tube skeleton
Key Technical Features
Frequency Characteristics
Wide operating range: 20-300Hz
Rated frequency: 22Hz
Independent HV winding design
Cooling System
ONAN cooling (Oil Natural Air Natural)
Class A heat resistance
25# transformer oil
Temperature limits: Winding ≤65K, Oil ≤55K
Structural Design
Steel housing with wheels
Shell-type oil tank with conservator
30kV corona-free bushings
Sound level: 65dB
Protection System
Electrical Protection:
Piezoresistors on HV outputs
Zinc oxide arresters for grounding
Fiber glass bushings with corona rings
Insulation Protection:
Balanced electrostatic shielding
Flashover prevention system
Partial discharge reduction design
Performance Specifications
Parameter | Value |
---|---|
Maximum Output Voltage | 30kV (corona-free) |
Frequency Range | 20-300Hz |
Cooling Method | ONAN |
Working Cycle | Matched to reactor specifications |
Typical Applications
Variable frequency resonant testing
Power transformer frequency response analysis
High-voltage cable testing
Rotating machine testing
Specialized research applications
Safety Features
30kV corona-free guaranteed operation
Thermal monitoring with automatic shutdown
Protected against external potential surges
Copper lead wire winding for reliability
The HET 90kVA variable frequency exciter transformer combines wide-frequency operation with high-voltage output capability, making it ideal for specialized testing applications requiring flexible frequency excitation.