≤100kVA Range
HET 60kVA Dual-Output Exciter Transformer (2×10kV)
Designed for demanding test environments, the HET 60kVA exciter transformer delivers dual 10kV outputs with <5pC partial discharge performance. Features ONAN cooling and zinc oxide overvoltage protection for reliable operation in industrial and laboratory settings.
Technical Specifications
Electrical Parameters | |
---|---|
Rated Capacity | 60kVA |
Input Voltage (LV) | 0.38kV |
Output Voltage (HV) | 2×10kV (configurable) |
Current Ratings | 157.9A (LV) / 3A-6A (HV) |
Frequency | 50Hz |
Partial Discharge | <5pC |
Performance Metrics
Temperature Rise: Continuous operation rated
Noise Level: ≤60dB at 1m distance
Corona Free: Verified at 20kV
Key Design Features
Advanced Insulation System
Electrostatic Shielding: HV-LV winding isolation layer
Cylinder-Type Windings: Balanced area distribution
Compound Insulation Tube: Reduces PD and shields core
Voltage Stabilization: Electrostatic compensation technology
Mechanical Construction
ONAN Cooling: Oil Natural Air Natural system
Steel Housing: Shell-type oil tank with conservator
Mobile Design: Wheel-mounted movable base
Fiberglass Bushings: 20kV corona-free operation
Protection Systems
Electrical Protection
Zinc oxide arresters on all HV outputs
Piezoresistors per HV terminal
Isovolumetric capacitance core
Structural Safety
Porcelain LV bushings
Multi-layer turn insulation
Flashover protection for all insulation
Performance Benefits
Dual-Output Flexibility: Parallel/series configuration options
Ultra-Low Noise: 60dB operational ceiling
Reliable Cooling: ONAN system for continuous operation
Field Deployment: Wheeled design for test site mobility
Typical Applications
Power transformer factory testing
High-voltage cable qualification
Industrial equipment dielectric tests
Research lab voltage generation
Compliant with IEC 60076-11 (dry-type) and IEEE C57.12.01 (liquid-immersed) standards. Recommended calibration interval: 18 months.