≤100kVA Range
HET 60kVA Triple-Range Exciter Transformer (5kV-15kV)
Engineered for versatile high-voltage applications, the HET 60kVA exciter transformer delivers three precision outputs (5kV/10kV/15kV) with <10pC partial discharge at rated voltage. Features ONAN cooling and advanced electrostatic shielding for laboratory and industrial testing.
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 60kVA |
Input Voltage (LV) | 0.4kV |
Output Voltage (HV) | 5kV / 10kV / 15kV |
Current Ratings | 150A (LV) / 4A (HV) |
Frequency | 50Hz |
Impedance Voltage | <5% |
Partial Discharge | <10pC at rated voltage |
Core Design Features
Advanced Insulation System
Electrostatic Shielding: Dedicated layer between HV windings
Cylinder-Type Windings: Balanced top/bottom area distribution
Compound Insulation Tube: Reduces partial discharge and shields iron core
Voltage Stabilization: Electrostatic compensation for uniform distribution
Mechanical Construction
ONAN Cooling: Oil Natural Air Natural system
Steel Housing: Shell-type oil tank with conservator
Mobile Design: Wheel-mounted with movable base
Corona-Free Bushings: Fiberglass HV bushings (15kV rated)
Protection Systems
Electrical Protection
Zinc oxide arresters on all HV outputs
Piezoresistors per HV terminal
Isovolumetric capacitance core for bushings
Structural Safety
Porcelain LV bushings
Multi-layer turn-to-turn insulation
Flashover protection for main/minor insulation
Performance Advantages
Triple Voltage Output: Single-unit solution for multiple test scenarios
Low Impedance: <5% voltage drop ensures accuracy
Corona-Free Operation: Verified at 15kV
Field Deployment: Wheeled design for test site mobility
Typical Applications
Power transformer testing
High-voltage cable evaluation
Industrial equipment dielectric tests
Research lab voltage generation
Complies with IEC 60076-3 insulation standards and IEEE C57.12.00 safety requirements. Recommended maintenance interval: 2 years or 2000 operational hours.