HET 41.5kVA Triple-Range Exciter Transformer (24kV/12kV/6kV) – Technical Specifications
Product Overview
The HET 41.5kVA exciter transformer provides three voltage ranges (24kV/12kV/6kV) in a single unit, featuring ultra-low partial discharge (<5pC) and <5% impedance. With ONAN cooling and advanced electrostatic shielding, it meets IEC 60076-11 standards for precision high-voltage testing.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 41.5kVA |
Input Voltage | 0.415kV |
Input Current | 100A |
Output Configurations: | |
• Ultra-HV Range | 24kV @ 1.73A |
• High Range | 12kV @ 3.46A |
• Standard Range | 6kV @ 6.92A |
Frequency | 50Hz ±1% |
Impedance Voltage | <5% |
Partial Discharge | <5pC at rated voltage |
Advanced Design Features
Triple-Voltage Operation
Independent winding taps for each voltage range
Precision voltage ratio (±0.5% accuracy)
No-load tap changer for safe switching
Dielectric Performance
24kV corona-free bushings with triple corona rings
Electrostatic shielding between all windings
Isovolumetric capacitance cores for stable voltage distribution
Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (20kA rating per IEC 60099-4)
Dual grounding points with 10mm² copper straps
2. Insulation Monitoring
Inter-turn insulation (2mm Nomex® layers)
Winding temperature sensors with alarm contacts
Oil level indicator with minimum mark
Mechanical Construction
Enclosure Features
12-gauge steel tank with ANSI 61 gray finish
Heavy-duty wheel base (4× 250mm casters with brakes)
Shell-type oil tank with 60L conservator
Terminal Configuration
LV terminals: Porcelain bushings (creepage ≥25mm/kV)
HV terminals: Fiberglass-reinforced epoxy bushings
All bushings have grading rings for field control
Installation & Maintenance
Commissioning Requirements
Minimum 1.5m clearance from grounded surfaces
Initial oil BDV ≥50kV (2.5mm gap)
Pre-operation IR ≥10,000MΩ (2.5kV megger)
Service Schedule
Monthly: Inspect bushing contamination
Quarterly: Oil DGA and moisture analysis
Annual: Complete winding resistance test
Typical Applications
Extra-high voltage cable testing
GIS (Gas Insulated Switchgear) commissioning
Power transformer routine tests
Research labs requiring multi-voltage testing