HET 40kVA Dual-Voltage Exciter Transformer (10kV/5kV) – Technical Specifications & Applications
Product Overview
The HET 40kVA exciter transformer delivers precision testing with dual-voltage outputs (10kV/5kV) and ultra-low partial discharge (<5pC). Designed with ONAN cooling and advanced electrostatic shielding, it complies with IEC 60076-11 for demanding high-voltage applications.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 40kVA |
Input Voltage | 0.4kV |
Input Current | 100A |
Output Configurations: | |
• High Range | 10kV @ 4A |
• Standard Range | 5kV @ 8A |
Frequency | 60Hz ±1% |
Impedance Voltage | <5% |
Partial Discharge | ≤5pC at rated voltage |
Key Features
Dual-Voltage Operation
Tap-selected outputs without manual reconfiguration
Common LV winding with multi-tap HV design
Automatic voltage stabilization during switching
Thermal Performance
ONAN cooling with 25# transformer oil
Continuous operation at full rated capacity
Winding temperature rise ≤65K
Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (15kA rating, IEC 60099-4)
Dual ground reference points for operator safety
2. Insulation Control
10kV corona-free fiberglass bushings
Electrostatic shielding between all windings
Isovolumetric capacitance cores in HV bushings
Mechanical Design
Enclosure Features
12-gauge steel housing with corrosion-resistant coating
Wheel-mounted (4× industrial casters with brakes)
Shell-type oil tank with 50L conservator
Terminal Configuration
LV terminals: High-creepage porcelain bushings
HV terminals: Fiberglass-reinforced epoxy bushings
All bushings feature dual corona rings
Winding Technology
Cylinder-type windings with balanced capacitance
Electrostatic compensation for uniform voltage gradient
Inter-turn insulation (1.5mm Nomex® layers)
Compound insulation tubes for partial discharge control
Installation & Maintenance
Commissioning Requirements
Minimum 1.2m clearance from grounded objects
Initial oil BDV ≥45kV (2.5mm gap)
Pre-operation IR ≥8,000MΩ
Service Schedule
Monthly: Bushing contamination inspection
Quarterly: Oil dielectric strength testing
Annual: Complete winding resistance test
Typical Applications
Power cable withstand testing
GIS (Gas Insulated Switchgear) commissioning
Transformer impulse testing systems
High-voltage component research & development