≤100kVA Range
HET 30kVA Triple-Voltage Exciter Transformer (20kV/10kV/5kV) – Technical Datasheet
Product Overview
The HET 30kVA exciter transformer provides three voltage ranges (20kV/10kV/5kV) with dual-frequency capability (50Hz/200Hz). Designed with electrostatic shielding and ONAN cooling, it meets IEC 60076-11 standards for precision high-voltage testing applications.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 30kVA |
Input Voltage | 0.35kV |
Input Current | 85.7A |
Output Configurations: | |
• High Range | 20kV @ 1.5A |
• Mid Range | 10kV @ 3A |
• Standard Range | 5kV @ 6A |
Frequency Range | 50Hz / 200Hz |
Impedance Voltage | <5% |
Advanced Features
Triple-Voltage Operation
Tap-selected outputs without manual reconfiguration
Common LV winding with multi-tap HV design
Automatic voltage stabilization during switching
Dual-Frequency Performance
Optimized for both power frequency (50Hz) and intermediate frequency (200Hz) testing
Special laminated core design to reduce eddy losses
Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (20kA rating, IEC 60099-4)
Dual ground reference points for operator safety
2. Insulation Control
20kV corona-free fiberglass bushings
Electrostatic shielding between all windings
Isovolumetric capacitance cores in HV bushings
Mechanical Construction
Enclosure Features
12-gauge steel tank with ANSI 61 gray finish
Quad-wheel base with locking casters (250mm)
Shell-type oil tank with 50L conservator
Terminal Configuration
LV terminals: High-creepage porcelain bushings
HV terminals: Triple-tap fiberglass bushings
All bushings feature dual corona rings
Winding Technology
Cylinder-type windings with balanced capacitance
Electrostatic compensation for uniform voltage gradient
Inter-turn insulation (1.5mm Nomex® layers)
Compound insulation tubes for partial discharge control
Installation & Maintenance
Commissioning Requirements
Minimum 1.2m clearance from grounded objects
Initial oil BDV ≥50kV (2.5mm gap)
Pre-operation IR ≥10,000MΩ
Service Schedule
Monthly: Bushing contamination inspection
Quarterly: Oil dielectric strength testing
Annual: Complete winding resistance test
Typical Applications
Multi-voltage cable withstand testing
GIS (Gas Insulated Switchgear) commissioning
Transformer impulse testing systems
High-voltage component research & development