HET 30kVA Triple-Range Exciter Transformer (2.5kV/1.5kV/0.75kV) – Complete Technical Guide
Product Overview
The HET 30kVA exciter transformer offers three selectable voltage outputs (2.5kV/1.5kV/0.75kV) in a single compact unit. With ultra-low impedance (<3%) and ONAN cooling, it's ideal for precision testing across multiple voltage requirements while complying with IEC 60076-11 standards.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 30kVA |
Input Voltage | 0.4kV |
Input Current | 75A |
Output Configurations: | |
• High Range | 2.5kV @ 12.9A |
• Mid Range | 1.5kV @ 19.375A |
• Standard Range | 0.75kV @ 38.75A |
Frequency | 50Hz ±1% |
Impedance Voltage | <3% (lowest in class) |
Advanced Design Features
Triple-Voltage Operation
Tap-selected outputs without external reconfiguration
Common LV winding with multiple HV winding taps
Auto-synchronized voltage switching
Thermal Management
Continuous duty cycle matching reactor operation
ONAN cooling with 25# transformer oil
Optimized oil flow through shell-type tank design
Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV output taps
Zinc oxide arresters (15kA rating) on I/O terminals
Dual ground reference points for operator safety
2. Insulation Control
Electrostatic shielding between all windings
2.5kV corona-free fiberglass bushings
Inter-turn barriers (1mm Nomex®) for flashover prevention
Mechanical Construction
Enclosure Features
14-gauge steel housing with corrosion-resistant coating
Integrated wheel base (4× 200mm industrial casters)
Shell-type oil tank with 35L conservator
Terminal Configuration
LV terminals: High-creepage porcelain bushings
HV terminals: Triple-tap fiberglass bushings
All bushings feature dual corona rings
Winding Technology
Cylinder-type windings with precision area matching (±2%)
Electrostatic compensation for uniform voltage distribution
Compound insulation tubes with partial discharge
<5pc<>Isovolumetric capacitance cores in all HV bushings
Installation & Maintenance
Commissioning Requirements
Minimum 800mm clearance from grounded surfaces
Initial oil BDV ≥40kV (2.5mm gap)
Pre-operation IR ≥5,000MΩ
Service Schedule
Monthly: Visual inspection of bushings and corona rings
Bi-annual: Oil dielectric strength testing
Annual: Winding resistance measurement
Typical Applications
Multi-voltage cable testing systems
Transformer factory acceptance testing
Rotating machine insulation diagnostics
Research labs requiring flexible test voltages