HET 25kVA High-Voltage Exciter Transformer (12.5kV/6.25kV) – Technical Datasheet
Product Overview
The HET 25kVA exciter transformer is engineered for precision high-voltage testing with dual-range outputs (12.5kV/6.25kV). Featuring ultra-low partial discharge (<2pC) and advanced electrostatic shielding, it complies with IEC 60076-11 for dielectric testing in high-voltage laboratories and industrial facilities.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 25kVA |
Input Voltage | 0.4kV |
Input Current | 62.5A |
Output Configurations: | |
• High Range | 12.5kV @ 2A |
• Standard Range | 6.25kV @ 4A |
Frequency | 50Hz ±0.5% |
Impedance Voltage | <4% |
Partial Discharge | <2pC at rated voltage (IEC 60270) |
Advanced Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (IEC 60099-4 compliant)
Ground-connected via 15kA surge arresters
2. Insulation & Discharge Control
12.5kV corona-free HV bushings
Electrostatic shield layer between HV windings
Isovolumetric capacitance cores for stable voltage gradient
Mechanical Construction
Enclosure Features
Steel housing with epoxy powder coating
Wheel-mounted (4× heavy-duty casters)
Shell-type oil tank with 40L conservator
Terminal Configuration
LV terminals: Porcelain bushings
HV terminals: Fiberglass-reinforced bushings
Dual corona rings per HV bushing
Winding Technology
Advanced Insulation
Cylinder-type winding with balanced top/bottom capacitance
Inter-turn insulation (1.2mm Nomex® layers)
Electrostatic compensation shields for uniform voltage distribution
Dielectric Performance
Impulse withstand: 150kV (1.2/50μs wave)
Power frequency withstand: 30kV/min
Partial discharge <2pC at 1.1Ur
Installation & Maintenance
Commissioning Requirements
Minimum 1.5m clearance from grounded objects
Oil dielectric strength ≥55kV before energization
Initial insulation resistance ≥12,000MΩ
Service Schedule
Semi-annual oil testing (BDV, moisture content)
Bushing inspection every 3 months
Winding resistance test every 5,000 operating hours
Typical Applications
Power transformer factory acceptance tests
GIS (Gas Insulated Switchgear) commissioning
High-voltage cable partial discharge measurement
Rotating machine insulation diagnostics