HET 25kVA/20kV Exciter Transformer – Technical Specifications & High-Voltage Testing Guide

Industrial-grade 25kVA exciter transformer with 20kV/10kV outputs, electrostatic shielding, and zinc oxide surge protection. Ideal for high-voltage testing up to 60kV with water termination.


  • US$ 4,803.00
  • Lead time: 30 day

>>>WhatsApp Communication<<<

Product Details

Product Tags

HET 25kVA/20kV Exciter Transformer – Technical Specifications & High-Voltage Testing Guide

Product Overview

The HET 25kVA exciter transformer is engineered for precision high-voltage testing with dual-range outputs (20kV/10kV) and extended capability up to 60kV with water termination. Featuring ONAN cooling and advanced electrostatic shielding, it complies with IEC 60076-11 for demanding industrial applications.

Electrical Specifications

ParameterSpecification
Rated Capacity25kVA
Input Voltage10kV
Input Current50A
Output Configurations:
• Standard Range20kV @ 4A
• Extended Range (water term.)60kV @ 1.33A
Frequency50Hz ±1%
Impedance Voltage<6%

Advanced Protection Systems

1. Overvoltage Protection

  • Piezoresistors on all HV outputs

  • Zinc oxide arresters (25kA rating, IEC 60099-4)

  • Ground-connected via Class 2 surge arresters

2. Insulation & Discharge Control

  • 20kV corona-free HV bushings

  • Electrostatic shield layer between HV windings

  • Isovolumetric capacitance cores for stable voltage distribution

Mechanical Construction

Enclosure Features

  • 12-gauge steel housing with ANSI 49 finish

  • Heavy-duty wheel base (4× 250mm casters)

  • Shell-type oil tank with 50L conservator

Terminal Configuration

  • LV terminals: High-strength porcelain bushings

  • HV terminals: Fiberglass-reinforced epoxy bushings

  • Dual corona rings per HV bushing

Winding Technology

Advanced Insulation

  • Cylinder-type winding with balanced capacitance

  • Inter-turn insulation (2mm Nomex® layers)

  • Electrostatic compensation shields

Dielectric Performance

  • Impulse withstand: 200kV (1.2/50μs wave)

  • Power frequency withstand: 45kV/min

  • Partial discharge <5pC at 1.1Ur

Water Termination Testing

60kV Configuration

  • Requires deionized water tank termination

  • Minimum 2m clearance from ground

  • Special 13.7kV tap input configuration

Safety Protocols

  • Use Class 4 HV gloves during setup

  • Verify water resistivity ≥5MΩ-cm

  • Install grading rings on test object

Maintenance Schedule

Routine Service

  • Monthly: Bushing visual inspection

  • Quarterly: Oil dielectric strength test

  • Annual: Winding resistance measurement

Critical Checks

  • Verify arrester leakage current every 500 hours

  • Monitor oil conservator level weekly

  • Test ground continuity before each use