≤100kVA Range
HET 25kVA/20kV Exciter Transformer – Technical Specifications & High-Voltage Testing Guide
Product Overview
The HET 25kVA exciter transformer is engineered for precision high-voltage testing with dual-range outputs (20kV/10kV) and extended capability up to 60kV with water termination. Featuring ONAN cooling and advanced electrostatic shielding, it complies with IEC 60076-11 for demanding industrial applications.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 25kVA |
Input Voltage | 10kV |
Input Current | 50A |
Output Configurations: | |
• Standard Range | 20kV @ 4A |
• Extended Range (water term.) | 60kV @ 1.33A |
Frequency | 50Hz ±1% |
Impedance Voltage | <6% |
Advanced Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (25kA rating, IEC 60099-4)
Ground-connected via Class 2 surge arresters
2. Insulation & Discharge Control
20kV corona-free HV bushings
Electrostatic shield layer between HV windings
Isovolumetric capacitance cores for stable voltage distribution
Mechanical Construction
Enclosure Features
12-gauge steel housing with ANSI 49 finish
Heavy-duty wheel base (4× 250mm casters)
Shell-type oil tank with 50L conservator
Terminal Configuration
LV terminals: High-strength porcelain bushings
HV terminals: Fiberglass-reinforced epoxy bushings
Dual corona rings per HV bushing
Winding Technology
Advanced Insulation
Cylinder-type winding with balanced capacitance
Inter-turn insulation (2mm Nomex® layers)
Electrostatic compensation shields
Dielectric Performance
Impulse withstand: 200kV (1.2/50μs wave)
Power frequency withstand: 45kV/min
Partial discharge <5pC at 1.1Ur
Water Termination Testing
60kV Configuration
Requires deionized water tank termination
Minimum 2m clearance from ground
Special 13.7kV tap input configuration
Safety Protocols
Use Class 4 HV gloves during setup
Verify water resistivity ≥5MΩ-cm
Install grading rings on test object
Maintenance Schedule
Routine Service
Monthly: Bushing visual inspection
Quarterly: Oil dielectric strength test
Annual: Winding resistance measurement
Critical Checks
Verify arrester leakage current every 500 hours
Monitor oil conservator level weekly
Test ground continuity before each use