≤100kVA Range
HET 25kVA/16kV Exciter Transformer - Technical Specifications & Ultra-HV Testing Capabilities
Product Overview
The HET 25kVA exciter transformer is engineered for demanding high-voltage testing applications up to 16kV, featuring dual-range outputs (16kV/8kV) and exceptional partial discharge performance (<5pc). with="">ONAN cooling and advanced electrostatic shielding, it complies with IEC 60076-11 and IEEE C57.12.00 standards.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 25kVA |
Input Voltage | 0.4kV |
Input Current | 62.5A |
Output Configurations: | |
• Ultra-HV Range | 16kV @ 1.56A |
• Standard Range | 8kV @ 3.125A |
Frequency | 50Hz ±0.5% |
Impedance Voltage | <4% |
Partial Discharge | <5pC at 100% rated voltage |
Advanced Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (20kA rating, IEC 60099-4 compliant)
Ground-referenced terminals via Class 1 surge arresters
2. Corona & Insulation Control
16kV corona-free HV bushings with triple corona rings
Isovolumetric capacitance cores for precise voltage distribution
Electrostatic shielding between all HV windings
Mechanical Construction
Enclosure Features
10-gauge steel housing with ANSI 61 gray finish
Industrial wheel base (4× 200mm casters with brakes)
Shell-type oil tank with 45L conservator and moisture indicator
Terminal Configuration
LV terminals: High-density porcelain bushings
HV terminals: Fiberglass-reinforced epoxy bushings
Voltage-graded creepage distance ≥35mm/kV
Winding Technology
Advanced Insulation
Cylinder-type winding with ±2% capacitance balance
Inter-turn insulation (1.5mm Nomex® 410 layers)
Electrostatic compensation shields with 5kV/mm gradient control
Dielectric Performance
Impulse withstand: 175kV (1.2/50μs wave)
Power frequency withstand: 35kV/min
Partial discharge <5pC at 1.1Ur per IEC 60270
Operational Parameters
Thermal Performance
Continuous operation: 100% load for 60 minutes
Winding temp rise ≤65K at rated load
Oil temp rise ≤55K at rated load
Environmental Specifications
Altitude: ≤1000m ASL
Ambient temperature: -25°C to +40°C
Relative humidity: ≤95% non-condensing
Maintenance Protocol
Routine Service
Oil testing: Quarterly BDV and moisture analysis
Bushing inspection: Monthly visual checks for carbon tracking
Winding resistance: Annual measurement with 100A micro-ohmmeter
Safety Procedures
Always discharge test object through 10kΩ/100W resistor
Verify ground connection integrity before operation
Use Class E HV gloves when adjusting bushings