HET 20kVA Multi-Tap Exciter Transformer (20kV/15kV/10kV) – Technical Datasheet

Industrial-grade 20kVA exciter transformer with 20kV/15kV/10kV selectable outputs, ONAN cooling, and <10pC partial discharge. Features zinc oxide surge arresters and corona-free bushings for high-voltage testing.


  • US$ 3,874.00
  • Lead time: 30 day

>>>WhatsApp Communication<<<

Product Details

Product Tags

HET 20kVA Multi-Tap Exciter Transformer (20kV/15kV/10kV) – Technical Datasheet

Product Overview

The HET 20kVA exciter transformer is a heavy-duty, single-phase unit designed for precision high-voltage testing with three selectable outputs (20kV/15kV/10kV). Engineered with ONAN cooling and advanced electrostatic shielding, it complies with IEC 60076-11 for dielectric testing in power utilities and industrial labs.

Electrical Specifications

ParameterValue
Rated Capacity20kVA
Input Voltage380V ±10%
Output Taps:
• Tap 1 (High Range)20kV @ 1A
• Tap 2 (Mid Range)15kV @ 1.33A
• Tap 3 (Standard)10kV @ 2A
Cooling MethodONAN (Oil Natural Air Natural)
Partial Discharge<10pC at rated voltage

Protection Systems

1. Overvoltage Protection

  • Piezoresistors on all HV outputs

  • Zinc oxide arresters (IEC 60099-4) on terminals

  • Ground-connected via 20kA surge arresters

2. Corona & Insulation Control

  • 20kV corona-free HV bushings

  • Isovolumetric capacitance cores for stable voltage gradient

  • Dual corona rings per bushing

Mechanical Design

Enclosure Features

  • 12-gauge steel housing with corrosion-resistant coating

  • Wheel-mounted (4× heavy-duty casters)

  • Shell-type oil tank with 50L conservator

Terminal Configuration

  • LV terminals: Porcelain bushings (380V input)

  • HV terminals: Fiberglass-reinforced bushings

  • Voltage-graded insulation for all taps

Winding Technology

Advanced Insulation

  • Cylinder-type winding with balanced capacitance distribution

  • Electrostatic shields between HV/LV windings

  • Inter-turn insulation (0.75mm Nomex® layers)

Dielectric Performance

  • Impulse withstand: 125kV (1.2/50μs wave)

  • Power frequency withstand: 25kV/min

  • Partial discharge <10pC per IEC 60270

Installation & Maintenance

Commissioning Requirements

  • Minimum 1.2m clearance from grounded objects

  • Oil dielectric strength ≥50kV pre-energization

  • Initial insulation resistance ≥10,000MΩ

Service Schedule

  • Bi-annual oil analysis (BDV, moisture content)

  • Bushing torque check every 12 months

  • Winding resistance test every 5,000 operating hours

Typical Applications

  • Power transformer routine testing

  • GIS (Gas Insulated Switchgear) commissioning

  • Rotating machine insulation testing

  • High-voltage cable factory acceptance tests