HET 20kVA Multi-Tap Exciter Transformer (20kV/15kV/10kV) – Technical Datasheet
Product Overview
The HET 20kVA exciter transformer is a heavy-duty, single-phase unit designed for precision high-voltage testing with three selectable outputs (20kV/15kV/10kV). Engineered with ONAN cooling and advanced electrostatic shielding, it complies with IEC 60076-11 for dielectric testing in power utilities and industrial labs.
Electrical Specifications
Parameter | Value |
---|---|
Rated Capacity | 20kVA |
Input Voltage | 380V ±10% |
Output Taps: | |
• Tap 1 (High Range) | 20kV @ 1A |
• Tap 2 (Mid Range) | 15kV @ 1.33A |
• Tap 3 (Standard) | 10kV @ 2A |
Cooling Method | ONAN (Oil Natural Air Natural) |
Partial Discharge | <10pC at rated voltage |
Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (IEC 60099-4) on terminals
Ground-connected via 20kA surge arresters
2. Corona & Insulation Control
20kV corona-free HV bushings
Isovolumetric capacitance cores for stable voltage gradient
Dual corona rings per bushing
Mechanical Design
Enclosure Features
12-gauge steel housing with corrosion-resistant coating
Wheel-mounted (4× heavy-duty casters)
Shell-type oil tank with 50L conservator
Terminal Configuration
LV terminals: Porcelain bushings (380V input)
HV terminals: Fiberglass-reinforced bushings
Voltage-graded insulation for all taps
Winding Technology
Advanced Insulation
Cylinder-type winding with balanced capacitance distribution
Electrostatic shields between HV/LV windings
Inter-turn insulation (0.75mm Nomex® layers)
Dielectric Performance
Impulse withstand: 125kV (1.2/50μs wave)
Power frequency withstand: 25kV/min
Partial discharge <10pC per IEC 60270
Installation & Maintenance
Commissioning Requirements
Minimum 1.2m clearance from grounded objects
Oil dielectric strength ≥50kV pre-energization
Initial insulation resistance ≥10,000MΩ
Service Schedule
Bi-annual oil analysis (BDV, moisture content)
Bushing torque check every 12 months
Winding resistance test every 5,000 operating hours
Typical Applications
Power transformer routine testing
GIS (Gas Insulated Switchgear) commissioning
Rotating machine insulation testing
High-voltage cable factory acceptance tests