≤100kVA Range
HET 15kVA/6kV Exciter Transformer – Full Specifications & Safety Features
Product Overview
The HET 15kVA/6kV Exciter Transformer is a high-efficiency, single-phase unit designed for precision high-voltage testing up to 6kV. Featuring ONAN cooling, ultra-low noise (<60db), and="" advanced="" electrostatic="" shielding="">IEC 60076-11 standards for test transformers.
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 15kVA |
Frequency Range | 50Hz–300Hz |
Input Voltage | 2×460V / 2×500V |
Input Current | 2×16.3A |
Output Voltage | 6kV |
Output Current | 2.5A |
Impedance Voltage | <6% |
Voltage Ratio Error | ±0.5% |
Partial Discharge | <10pC at 100% rated voltage |
Temperature Rise | Winding ≤65K, Oil ≤55K |
Key Protection Systems
1. Overvoltage & Surge Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (IEC 60099-4 compliant) on input/output terminals
Ground-referenced terminals for operator safety
2. Corona & Discharge Control
6kV corona-free HV bushings
Dual corona rings per bushing
Isovolumetric capacitance core for stable voltage distribution
Mechanical Design
Enclosure Features
Steel housing with epoxy-coated finish
Wheel-mounted for portability (4× industrial casters)
Shell-type oil tank with conservator
Terminal Configuration
LV terminals: Porcelain bushings
HV terminals: Fiberglass-reinforced bushings
Voltage-graded insulation for all outputs
Winding & Insulation
Advanced Winding Technology
Cylinder-type winding with balanced top/bottom capacitance
Electrostatic shielding between HV/LV windings
Inter-turn insulation to prevent flashover
Dielectric Performance
Partial discharge <10pC (IEC 60270)
Impulse withstand: 95kV (1.2/50μs wave)
Power frequency withstand: 15kV/min
Operational Guidelines
Installation Requirements
Minimum 1m clearance from grounded surfaces
Ambient temperature: -20°C to +45°C
Oil dielectric strength ≥45kV before use
Maintenance Protocol
Annual oil testing (breakdown voltage, acidity)
Bushing inspection every 6 months
Winding resistance check every 2 years
Typical Applications
Power cable hipot testing
Switchgear commissioning tests
Rotating machine excitation systems
High-voltage component R&D