Water Conditioning Unit
CTS 120kW Water Conditioning Unit
Primary Application: Thermal management for 400kV-class cable termination testing systems
Core Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Power Input | 220V±10%/20A, 50/60Hz | IEC 60364 |
Cooling Capacity | 120 kW (peak) | ISO 5151 |
Water Volume | 500 liters | - |
System Pressure | 4 atm (400 kPa max) | ASME BPVC |
Hydraulic System Details
Flow Characteristics
Min Flow Velocity: 45 L/min
Pipe Connections: 2× 1" main ports
Header Size: ¾" NPT
Water Quality
Resistivity: >2 MΩ·cm
Conductivity: 0.1-2 μS/cm
TDS: <1 ppm
Safety & Protection Systems
Multi-Stage Protection:
Low-water cutoff (level sensor)
Pump reversal interlock (sequence editor)
Over-temperature shutdown (>60°C)
Dual-pressure relief valves
Emergency Features:
Manual bypass valve
Ground fault interrupter
Visual/audible alarms
Environmental Specifications
Parameter | Operating Range | Shutdown Threshold |
---|---|---|
Ambient Temperature | +3°C to +35°C | <0°C or >40°C |
Coolant Temperature | ≤20°C (inlet) | >60°C (system) |
Note: External chiller required when ambient >35°C for continuous 120kW operation
Physical Configuration
Dimensions: 1200×1400×1700 mm (L×W×H)
Weight: 272 kg (dry), ≈800 kg (operational)
Clearance Requirements:
500mm rear/sides for maintenance
1m overhead for pipe access
Maintenance Protocol
Daily: Check conductivity and water level
Weekly: Inspect pipe fittings for leaks
Monthly: Test safety interlocks
Annually: Replace deionization cartridges