HET 30kVA Variable Frequency Exciter Transformer (1.5kV/0.35kV) – Technical Specifications
Product Overview
The HET 30kVA exciter transformer is engineered for precision testing across a wide frequency range (30-300Hz), delivering dual voltage outputs (1.5kV/0.35kV). With ONAN cooling and ultra-low partial discharge (<5pC), it supports continuous operation at full rated capacity.
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 30kVA |
Frequency Range | 30-300Hz |
Input Voltage | 350V |
Input Current | 85.7A (max) |
Short Circuit Impedance | ≤5% |
Partial Discharge | ≤5pC |
Noise Level | ≤65dB |
Thermal Performance
Continuous operation at rated voltage/current
Winding temperature rise: ≤65K
Oil temperature rise: ≤55K
Cooling method: ONAN (Oil Natural Air Natural)
Advanced Protection Systems
1. Overvoltage Protection
Piezoresistors on all HV outputs
Zinc oxide arresters (IEC 60099-4 compliant)
Ground-connected via 15kA surge arresters
2. Insulation & Discharge Control
1.5kV corona-free HV bushings
Electrostatic shield layer between windings
Isovolumetric capacitance cores
Mechanical Design
Enclosure Features
Steel housing with corrosion-resistant coating
Wheel-mounted (4× industrial casters with brakes)
Shell-type oil tank with 40L conservator
Terminal Configuration
LV terminals: High-strength porcelain bushings
HV terminals: Fiberglass-reinforced epoxy bushings
Corona rings on all HV bushings
Winding Technology
Cylinder-type winding with balanced capacitance
Electrostatic compensation shields
Inter-turn insulation (1.2mm Nomex® layers)
Compound insulation tube skeleton
Installation & Maintenance
Commissioning Requirements
Minimum 1m clearance from grounded surfaces
Oil dielectric strength ≥45kV before use
Initial insulation resistance ≥8,000MΩ
Service Schedule
Monthly: Bushing inspection
Quarterly: Oil testing (BDV, moisture)
Annual: Winding resistance measurement
Typical Applications
Variable frequency resonance testing systems
Power cable partial discharge measurement
Rotating machine insulation diagnostics
Transformer factory acceptance tests