High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

FRA for Zig-Zag Grounding Transformers: Detecting Winding Asymmetry and Core Damage

Views:4
Update time:2026-04-23

Zig-Zag Grounding Transformer FRA: Diagnosing Winding Asymmetry and Core Integrity

Zig-zag grounding transformers provide a low-impedance path for ground fault currents in ungrounded or high-resistance grounded systems. Their unique winding configuration—each phase has two halves on different core limbs, connected in a zig-zag pattern—creates a distinctive frequency response. A Transformer Frequency Response Analyzer is ideally suited to detect winding asymmetry, inter-turn faults, and core damage that compromise grounding performance.

Zig-Zag Transformer Construction and FRA Implications

Key design features affecting FRA:

  • Split windings per phase: Each phase consists of two equal winding halves on different core limbs. This creates a more complex frequency response than conventional transformers, with twice as many resonant peaks.

  • No secondary winding: Zig-zag grounding transformers have only primary windings; there is no secondary to provide capacitive inter-winding measurements.

  • Low zero-sequence impedance: The zig-zag connection cancels flux for zero-sequence currents, resulting in low impedance to ground. This affects low-frequency FRA (

    <500 hz="">
  • Continuous neutral current: In systems with harmonic distortion, neutrals may carry significant triplen harmonics, thermally stressing windings.

Expected FRA Signatures for Healthy Zig-Zag Transformers

A healthy zig-zag grounding transformer produces:

  • Low-frequency band (10 Hz – 1 kHz): Higher amplitude than conventional transformers (-10 to -20 dB vs. -30 to -40 dB) due to low zero-sequence impedance.

  • Mid-frequency band (1–100 kHz): Multiple resonant peaks (10–20 peaks) corresponding to individual winding halves and their interactions. Peaks are closely spaced (every 5–15 kHz).

  • High-frequency band (100 kHz – 10 MHz): Slower roll-off (15–20 dB per decade) than conventional transformers because the zig-zag connection maintains capacitive coupling across phases.

  • Phase-to-phase symmetry: In a healthy unit, FRA signatures of phases A, B, and C are highly symmetrical (CC > 0.95 between phases).

Detecting Winding Asymmetry

Winding asymmetry—a common failure mode in zig-zag transformers—appears as:

  • Asymmetrical phase-to-phase CC: For example, A vs. B CC = 0.97, B vs. C CC = 0.96, but A vs. C CC = 0.72. This indicates that Phase C is the outlier.

  • Split-winding imbalance: If one of the two winding halves of a phase is damaged, FRA will show a "split peak" where a single resonant peak becomes two closely spaced peaks (e.g., 25 kHz and 28 kHz instead of a single peak at 26 kHz).

  • Amplitude mismatch between phases: One phase showing 2–5 dB lower amplitude in the mid-band while others are normal.

Case Example: Inter-Turn Fault Detected by Asymmetry

A 2 MVA zig-zag grounding transformer in an industrial plant experienced unexplained neutral current imbalance. DGA showed trace acetylene (1 ppm). FRA testing revealed:

  • Phase A vs. B CC = 0.98

  • Phase B vs. C CC = 0.97

  • Phase A vs. C CC = 0.68

  • Phase C showed a 4 dB amplitude reduction in the 10–30 kHz band

This asymmetric pattern (one phase deviating) indicated a fault on Phase C. Internal inspection found two shorted turns on one of the Phase C winding halves. The shorted turns were repaired, and FRA returned to symmetrical. Without FRA, the inter-turn fault would have progressed to a phase-to-ground fault, potentially causing a plant shutdown.

Testing Protocol for Zig-Zag Transformers

Follow this specialized procedure:

  1. De-energize the transformer and disconnect from the bus. Open the neutral grounding connection as well.

  2. Perform end-to-end measurements on each phase (H1 to H0, H2 to H0, H3 to H0) just like a conventional transformer.

  3. Additionally, perform phase-to-phase measurements (H1-H2, H2-H3, H3-H1) to assess the zig-zag interaction.

  4. Compare phases using CC thresholds: healthy units have phase-to-phase CC > 0.95 in mid-band.

  5. If a baseline exists, compare each phase individually to its baseline.

Core Damage Detection

Zig-zag transformers have cores similar to conventional transformers but may experience unique core damage from:

  • Overvoltage during single-phase-to-ground faults (the healthy phases see 1.73× line-to-neutral voltage)

  • GIC (geomagnetically induced currents) in long transmission lines connected to the same bus

Core damage appears as:

  • Low-frequency band (10–500 Hz) amplitude reduction > 3 dB on all phases (symmetrical)

  • Phase shift > 10 degrees at 50/60 Hz (can be observed by comparing phase angle at power frequency)

  • Hysteresis: FRA differs between increasing-frequency and decreasing-frequency sweeps

Establishing Baselines for Grounding Transformers

Because zig-zag transformers are often installed in harsh environments (outdoor substations, industrial yards), establish baselines:

  • Factory baseline before shipment

  • Commissioning baseline after installation

  • Baseline after any fault event (e.g., cleared ground fault)

Correlating FRA with Ground Fault Performance

Monitor grounding transformer health by correlating FRA with:

  • Zero-sequence impedance measurements: A healthy zig-zag transformer has low Z0 (typically 1–5 ohms). FRA asymmetry often precedes Z0 increase.

  • Neutral current harmonics: If FRA shows asymmetry, check neutral current for triplen harmonics—asymmetry reduces cancellation, increasing harmonic current.

  • Ground fault relay logs: Frequent ground fault trips may correlate with FRA-detected winding asymmetry.

Practical Testing Considerations

Field testing of zig-zag transformers presents:

  • Neutral access: The neutral bushing (H0) is often grounded directly. Disconnect the ground strap for testing, but re-connect before energizing.

  • Small size: Many zig-zag transformers are dry-type or small oil-filled units (500 kVA – 5 MVA). Use portable FRA instruments with alligator clips.

  • Harmonic-rich environment: Industrial plants with VFDs and rectifiers inject harmonics. Perform FRA during plant shutdowns for clean measurements.

The Transformer Frequency Response Analyzer, applied with phase-to-phase comparison and split-winding analysis, provides essential diagnostics for zig-zag grounding transformers. For industrial and utility engineers responsible for system grounding integrity, FRA is the most sensitive tool for detecting inter-turn faults and winding asymmetry before they compromise ground fault protection.

Related News
Read More >>
FRA for Battery Energy Storage System (BESS) Transformers: Bi-Directional Power Flow and Cycling Effects FRA for Battery Energy Storage System (BESS) Transformers: Bi-Directional Power Flow and Cycling Effects
2026-04-23
Learn how Frequency Response Analyzer testing adapts to BESS trans···
FRA for Zig-Zag Grounding Transformers: Detecting Winding Asymmetry and Core Damage FRA for Zig-Zag Grounding Transformers: Detecting Winding Asymmetry and Core Damage
2026-04-23
Apply Frequency Response Analyzer testing to zig-zag grounding tra···
FRA for Step-Voltage Regulators: Detecting Tap Winding Damage in Pole-Mounted and Pad-Mounted Units FRA for Step-Voltage Regulators: Detecting Tap Winding Damage in Pole-Mounted and Pad-Mounted Units
2026-04-23
Apply Frequency Response Analyzer testing to step-voltage regulato···
FRA for Gas-Insulated Transformers (GIT): SF6 Environment Effects on Frequency Signatures FRA for Gas-Insulated Transformers (GIT): SF6 Environment Effects on Frequency Signatures
2026-04-22
Understand how Frequency Response Analyzer testing adapts to gas-i···

Leave Your Message