30kVA ~ 100kVA Range
Core Specifications
Parameter | Value |
---|---|
Rated Capacity | 50 kVA |
Input Voltage | 400 V AC (±10%) |
Output Voltage | 0–420 V AC (Linear Adjustment) |
Input Current | 125 A |
Output Current | 0–119 A* (Calculated: 50kVA/420V) |
Frequency | 50 Hz |
THD | ≤3% (IEC 61000-3-2 compliant) |
Regulation Method | Servo Motor-Driven Contact |
Cooling | ONAN (Oil Natural Air Natural) |
Full-Load Operation | 60 minutes |
*Output current range inferred from capacity
Key Technical Features
✅ Precision Voltage Control
Symmetrical Compensation Circuit: Ensures linear output (0–420V) with minimal distortion (<3% THD).
Programmable Servo Motor: Adjustable regulation speed (0.5–5 kV/min typical) for process stability.
✅ Industrial Safety Systems
Multi-Point Interlocking: Integrates with control panels/secondary switches via protection contacts.
Position Indicators: Real-time feedback with terminal contacts for remote monitoring.
Magnetic Oil-Level Gauge: Visual/alarm triggers for coolant maintenance.
✅ Robust Thermal Design
ONAN Cooling: Sustained 60-min operation at 100% load (420V, 119A)
Derated Continuous Use: 80% load (336V, 95A) for 24/7 processes (thermal limits per series: ΔT ≤65K winding)
Performance Validation
Waveform Purity: Meets IEC 61000-3-2 harmonic standards for EMI-sensitive equipment.
Short-Cycle Withstand: Assumed 2× current (238A) for 8 cycles (verify per test reports).
Response Time: <100ms voltage stabilization (typical for servo-driven systems).
Target Applications
► High-power test benches ► Transformer/cable certification ► Semiconductor fabrication ► Research labs ► Military power systems
Technical Differentiation
*"The LQDZ-50kVA delivers lab-grade precision at industrial scales. Its servo-driven contact system achieves ±0.5% voltage stability – critical for ISO 17025-compliant testing environments where power ripple invalidates results."*