>200kVA Range
LQLVF 400kVA/3kV Low Voltage Filter: Passive LC Network for High-Efficiency EMI Suppression
Advanced Passive Filter Technology
Utilizing a precision-engineered LC network for superior EMI suppression:
Series inductance: Low-loss ferromagnetic core design
Parallel capacitors: Self-healing metallized film technology
Low-pass filter topology with sharp roll-off characteristics
Low insertion loss (<0.5dB at 50Hz)
High attenuation efficiency across operational band
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 400kVA |
Rated Voltage | 3kV |
Current Rating | 133.3A |
Phase Configuration | Single Phase |
Frequency | 50Hz |
Attenuation Performance |
|
Optimized Attenuation Characteristics
Engineered frequency response for critical noise suppression:
40-100kHz band: >30dB attenuation (harmonic suppression)
100kHz-1MHz band: >50dB attenuation (RFI/EMI control)
80dB/decade roll-off rate
Resonance damping circuitry
Frequency-stable performance (±2% across load range)
Low-Loss Design Advantages
Maximizing system efficiency while providing EMI protection:
Core losses <0.8% at full load
Copper losses <0.5% at rated current
Total system efficiency >98.5%
Advanced cooling fins for natural convection
Temperature rise limited to 55°C at full load
Industrial Applications
Ideal for 3kV systems requiring efficient EMI suppression:
Industrial motor drives
Medium-voltage switchgear
Renewable energy inverters
Railway traction systems
Test laboratory power supplies
Mining power distribution
Passive Network Design Features
Robust and maintenance-free operation:
No active components - higher reliability
Fail-safe operation
No external power supply required
Wide temperature operation (-25°C to +65°C)
20-year design life expectancy
Installation & Maintenance Protocol
Simplified deployment for industrial environments:
Maintain minimum 200mm clearance for airflow
Use crimped connectors rated for 150A minimum
Verify torque values on terminals (45 N·m)
Perform annual visual inspection of components
Test insulation resistance every 3 years (≥500MΩ at 5kV DC)
Monitor attenuation performance every 5 years
Safety & Protection Systems
Engineered for reliable operation:
Internal discharge resistors for capacitors
Overvoltage protection (5kV/1min withstand)
Thermal fusing for capacitor banks
Corona-resistant encapsulation
IP54-rated enclosure
Compliance & Standards
Meets international requirements including:
IEC 61000-3-12 harmonic emissions
IEEE 519-2022 harmonic control
EN 60204-1 safety of machinery
IEC 60076-6 reactor standards
UL 508 industrial control equipment
For passive filter design guides or technical specifications, contact our engineering team. Performance validated per IEC 61000-4-7 measurement standards.