>200kVA Range
LQLVF 250kVA/2*657.9A Power Noise Filter: Ultra High-Current EMI Suppression with ONAN Cooling
Extreme Current Capability
Engineered for the most demanding industrial power applications:
1315.8A total current capacity (2×657.9A)
Low-impedance design (≤0.05mΩ)
Copper busbars with 200% short-circuit withstand
Dynamic response time <5ms for load variations
Parallel operation capability for higher current needs
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 250kVA |
Rated Voltage | Input/Output: 0.38kV |
Current Rating | 2 × 657.9A |
Frequency | 50Hz |
Phase Configuration | Single Phase |
Cooling System | ONAN (Oil Natural Air Natural) |
Duty Cycle | 15 min ON / 15 min OFF (48 cycles/day max) |
Insulation Level | 3kV/1min (no abnormal discharge) |
Partial Discharge | Background noise <2pC |
Installation | Pre-stage Cabinet |
Specialized Intermittent Duty Operation
Optimized for high-impact industrial processes:
15-minute full-power operation cycles
Maximum 48 cycles per day (24 hours operation)
Rapid thermal recovery during OFF cycles
Cycle counter with maintenance alerts
Thermal memory protection for sequential operations
Advanced ONAN Cooling Technology
High-performance thermal management for extreme currents:
Enhanced mineral oil formulation for rapid heat transfer
Temperature stabilization in <7 minutes after startup
Oversized radiators with optimized fin geometry
Nitrogen-blanketed expansion tank
Dual-path convection channels
Ultra-Low Partial Discharge Design
Premium EMI suppression for sensitive equipment:
Background PD level <2pC at rated voltage
Quadruple-shielded reactor construction
Corona-resistant epoxy encapsulation
Integrated PD monitoring ports
Validated per IEC 60270 measurement standards
Pre-Stage Cabinet Integration
Engineered for upstream power distribution:
Reinforced mounting system for heavy-duty installation
Front-access terminals with safety disconnects
Thermal alignment with cabinet ventilation
Vibration-dampened core mounting
HV cable entry points with 60mm knockouts
Industrial Applications
Ideal for extreme-current 0.38kV systems:
Industrial resistance welding systems
Large induction heating installations
Foundry arc furnace power conditioning
High-current test laboratories
Electrolytic process power systems
Heavy industrial machinery power lines
Installation & Maintenance Protocol
Critical guidelines for ultra high-current systems:
Verify cabinet structural integrity (min 5mm steel)
Use silver-plated copper connectors (≥99% conductivity)
Maintain minimum 600mm clearance for airflow
Torque power terminals to 120 N·m ±3%
Monitor oil quality quarterly (BDV ≥40kV)
Perform infrared thermography during operation
Calibrate cycle counter annually
Safety & Protection Systems
Engineered for extreme operational environments:
Explosion-resistant pressure relief system
Triple-redundant temperature monitoring
Arc-quenching containment chambers
Surge protection (25kV/20μs withstand)
Ground fault interlock system
IP55-rated enclosure with corrosion protection
Compliance & Standards
Meets international requirements including:
IEC 61000-3-12 harmonic emissions
IEEE 519-2022 harmonic control
EN 50588-1 medium-power transformers
IEC 60076-11 dry-type transformers
ANSI/IEEE C57.91 thermal loading guide
NFPA 70 (NEC) Article 450
For ultra high-current applications or custom duty cycle configurations, contact our engineering team. Performance validated per IEEE 1137-2018 test standards.