>200kVA Range
LQLVF 250kVA/2*416.6A Power Noise Filter: High-Current EMI Suppression with ONAN Cooling
Premium Broadband Noise Attenuation
Engineered for critical EMI suppression in industrial 0.6kV systems:
40KHz-100KHz range: >40dB attenuation
100KHz-2MHz range: >60dB attenuation (extended high-frequency coverage)
Ultra-low background partial discharge: <2pC
Dual-circuit design for balanced load distribution
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 250kVA |
Rated Voltage | Input/Output: 0.6kV |
Current Rating | 2 × 416.6A (833.2A total) |
Frequency | 50Hz |
Phase Configuration | Single Phase |
Cooling System | ONAN (Oil Natural Air Natural) |
Insulation Level | 3kV/1min (no abnormal discharge) |
Continuous Operation | 60 min at 100% rated load |
Installation | Pre-stage Cabinet |
Advanced ONAN Cooling Technology
Optimized thermal management for high-current applications:
Mineral oil insulation with natural convection cooling
Temperature rise limit: 65°C at full load
Designed for ambient temperatures up to 45°C
Expansion tank with nitrogen cushion
Optimized radiator fins for efficient heat dissipation
High-Current Dual-Circuit Design
Robust engineering for demanding industrial applications:
833.2A total current capacity (2×416.6A)
Low-impedance copper busbar design (≤0.08mΩ)
Copper windings with 200% short-circuit withstand
Dynamic load response time <5ms
Parallel operation capability for higher current needs
Ultra-Low Partial Discharge Design
Premium EMI suppression for sensitive equipment:
Background PD level <2pC at rated voltage
Triple-shielded reactor construction
Corona-resistant encapsulation technology
PD-monitoring test points integrated
Validated per IEC 60270 measurement standards
Pre-Stage Cabinet Integration
Optimized for installation in upstream power distribution:
Compact form factor for pre-stage cabinet retrofitting
Front-access terminals for maintenance access
Vibration-resistant mounting brackets
Thermal alignment with cabinet airflow patterns
Standardized cable entry points (50mm knockouts)
Industrial Applications
Ideal for 0.6kV systems in:
Industrial power distribution pre-stages
Large motor control centers
Foundry and smelting operations
High-power test facilities
Process manufacturing power systems
Heavy industrial equipment power lines
Installation & Maintenance Protocol
Ensure optimal performance in pre-stage cabinets:
Verify cabinet clearance ≥400mm for natural convection
Use compression lugs rated for 500A connections
Check oil dielectric strength ≥40kV before commissioning
Torque power terminals to 70 N·m ±5%
Perform semi-annual insulation resistance tests
Monitor oil temperature quarterly during peak loads
Conduct partial discharge scans annually
Safety & Protection Systems
Engineered for reliable high-current operation:
Pressure relief device with alarm contacts
Buchholz relay for gas detection
Dual RTD temperature sensors (oil and winding)
Surge protection (15kV/20μs withstand)
Automatic discharge circuit for capacitors
IP54-rated enclosure for industrial environments
Compliance & Standards
Meets international requirements including:
IEC 60076 power reactor standards
IEEE C57.12.00 liquid-immersed equipment
EN 50588-1 medium-power transformers
IEC 61000-3-12 harmonic emissions
ANSI/IEEE C57.91 thermal loading guide
UL 506 standard for power transformers
For pre-stage cabinet integration guides or custom high-current solutions, contact our engineering team. Performance validated per IEEE 1137-2018 test standards.