Proper transformer turns ratio (TTR) testing is fundamental to maintaining transformer reliability in high voltage systems. This comprehensive guide walks you through the complete testing process, from preparation to interpretation of results.
Turns ratio testing verifies the voltage transformation capability of power transformers by comparing primary and secondary winding ratios. This critical test helps identify:
Winding deformations or displacements
Shorted turns or open circuits
Incorrect tap changer operation
Manufacturing defects
Ensure transformer is de-energized and properly grounded
Verify test equipment calibration status
Record nameplate data (rated voltages, vector group, tap positions)
Connect TTR meter leads to HV and LV bushings
Ensure clean, tight connections to minimize contact resistance
Follow manufacturer's polarity markings
Start with nominal tap position
Apply test voltage (typically 8-120V AC)
Record ratio measurements for all phases
Repeat for all tap positions if applicable
Compare measured ratios against expected values:
Acceptable deviation: Typically ±0.5% of nameplate ratio
Warning signs: >1% deviation may indicate problems
Phase comparisons: Inter-phase differences should be minimal
TTR testing should comply with:
IEEE C57.12.90 - Test Code for Liquid-Immersed Transformers
IEC 60076-1 - Power Transformers General Requirements
ASTM D3612 - Standard Test Method for Analysis of Gases Dissolved in Electrical Insulating Oil
Inconsistent readings: Check connections and test lead resistance
High deviation: Investigate for winding defects or tap changer problems
No reading: Verify open circuit conditions
Always prioritize safety when performing TTR tests:
Use proper PPE (insulated gloves, safety glasses)
Follow lockout/tagout procedures
Maintain safe working distances
Be aware of capacitive discharge risks
Regular TTR testing forms the cornerstone of effective transformer maintenance programs, helping prevent costly failures in high voltage systems.