
Instrument transformers – current transformers (CTs) and voltage transformers (VTs) – are the eyes and ears of electrical protection and metering systems. Unlike power transformers, instrument transformers often operate for decades without maintenance, yet their failure can cause protection misoperation, revenue loss, and even busbar faults. A Tan Delta Tester (dissipation factor analyzer) provides the most practical on-site method for assessing instrument transformer insulation health without removal from service. This article covers specialized tan delta testing techniques for oil-filled, SF6-insulated, and dry-type CTs and VTs.
Instrument transformers face unique reliability challenges:
Continuous operation: CTs and VTs remain energized for decades without load cycling that might reveal problems.
Hermetic sealing: Many are sealed units – moisture ingress cannot be detected by oil sampling without breaking the seal.
High stress concentration: CT primary windings carry full line current while secondary circuits are low impedance, creating unique dielectric stress profiles.
Hidden failures: Internal insulation deterioration often remains undetected until catastrophic failure causes bushing explosion or fire.
Protection blind spots: A failed CT or VT can disable protection zones, leaving substation buses unprotected.
Tan delta testing identifies developing insulation problems before they escalate.
High voltage CTs (above 34.5 kV) typically use oil-impregnated paper (OIP) or SF6 insulation. Key test configurations:
C1 insulation: Between primary conductor and secondary windings (main insulation).
C2 insulation: Between secondary windings and ground (secondary insulation).
Bushing insulation: For draw-lead or top-core CTs, bushing insulation may be separate.
Using a tan delta tester, measure each insulation section independently. For OIP CTs, IEEE C57.13 recommends tan δ limits: C1 less than 0.5% (new) or 0.7% (in-service); C2 less than 0.8% (new) or 1.0% (in-service).
Modern VTs fall into two main categories:
Electromagnetic VTs (standard): Similar to small power transformers with primary and secondary windings. Test primary-to-secondary (C1) and secondary-to-ground (C2).
Capacitive VTs (CVTs): Contain a capacitive voltage divider (stack of capacitor units) plus an electromagnetic unit. Test individual capacitor elements and the electromagnetic unit separately.
For CVTs, pay special attention to the capacitor stack – tan δ values above 0.4% per capacitor unit indicate moisture ingress that can affect voltage division accuracy.
Follow this procedure for safe and accurate instrument transformer tan δ testing:
De-energize and isolate: Open primary disconnects and secondary circuits. Ensure CT secondary terminals are shorted before primary disconnection to avoid dangerous overvoltages.
Clean terminals: Remove dirt and oxidation from primary and secondary bushings.
Configure GST mode (grounded specimen test): For C1 measurement, apply high voltage to primary terminal, ground secondary terminals, and measure tan δ from primary to ground.
Configure UST mode (ungrounded specimen test): For C2 measurement, apply high voltage to secondary terminals (with primary grounded) or use guard techniques.
Record temperature: Measure bushing or tank surface temperature for correction to 20°C reference.
Normal ranges for OIP instrument transformers:
Tan δ (C1) less than 0.5%: Excellent condition
Tan δ (C1) 0.5% to 0.7%: Acceptable, but monitor annually
Tan δ (C1) 0.7% to 1.0%: Deterioration detected – investigate within 6 months
Tan δ (C1) greater than 1.0%: Immediate action required – high failure risk
For dry-type or resin-encapsulated CTs and VTs:
Tan δ less than 0.8%: Normal
Tan δ 0.8% to 1.5%: Monitor closely (semiannual)
Tan δ greater than 1.5%: Plan replacement
Capacitance changes exceeding ±3% from nameplate or baseline indicate physical movement, moisture, or internal shorted turns.
CVTs contain multiple capacitor units connected in series. Each unit should have consistent tan δ and capacitance. A useful diagnostic technique is to measure tan δ at both 50/60 Hz and at 0.1 Hz (if your tester supports VLF mode). Large differences between 60 Hz and 0.1 Hz tan δ suggest moisture-induced polarization effects. For dry capacitors, the frequency dependence is minimal. For wet or degraded paper capacitors, low-frequency tan δ may be 2-5 times higher than 60 Hz values.
Instrument transformers follow similar temperature dependence as power transformer insulation (k = 0.04 to 0.05 per °C). Use the Arrhenius-based correction: Tan δ(20°C) = Tan δ(T) × exp(-0.045 × (T - 20)).
Quick reference correction factors (OIP insulation):
Measured at 30°C → multiply by 0.63 to 0.65
Measured at 40°C → multiply by 0.40 to 0.42
Measured at 50°C → multiply by 0.25 to 0.27
Note: Many CTs and VTs operate near ambient temperature unless located in direct sunlight or near busbars. Measure actual bushing temperature – do not assume ambient equals insulation temperature.
A 138 kV substation had 24 oil-filled CTs. Annual tan δ testing revealed one CT with C1 tan δ trending: Year 1: 0.38%, Year 2: 0.42%, Year 3: 0.51%, Year 4: 0.67%, Year 5: 0.72%. While still below the 1.0% alarm threshold, the accelerating trend (0.04% increase in Year 3, 0.09% in Year 4) triggered investigation. DGA from an oil sample (drilled under controlled conditions) revealed high acetylene – internal arcing. The CT was replaced during a scheduled outage. Six months later, a sister CT without testing failed catastrophically, causing a bus fault and 8-hour outage. The monitored CT saved an estimated $1.2 million in repair and outage costs.
For SF6-insulated CTs and VTs (common in GIS substations), tan δ testing is equally important but presents unique considerations:
SF6 itself has excellent dielectric properties – tan δ is dominated by solid insulation (epoxy spacers and support insulators).
Expected tan δ values are typically lower than OIP – below 0.2% for new equipment.
Rising tan δ often indicates solid insulation contamination or partial discharge activity before breakdown.
Capacitance remains very stable in SF6 – changes above 1% suggest internal mechanical movement.
For GIS-embedded CTs, access may require special test adapters. Use manufacturer-provided test ports.
Establish risk-based intervals:
Critical protection zones (transmission substations, generator step-up): Test every 2 years.
Distribution substations (34.5 kV and below): Test every 4-5 years.
Revenue metering CTs/VTs: Test annually (accuracy affects billing).
After through-fault or nearby lightning strike: Test immediately.
Older units (over 30 years in service): Test annually regardless of criticality.
Mistake 1 – Forgetting CT secondary shorting: Open-circuiting CT secondary during primary de-energization (or even during testing) can generate lethal voltages. Always short CT secondaries before disconnecting primary.
Mistake 2 – Testing through surge arresters: Many CTs and VTs have internal or external surge arresters. Disconnect them – arresters dominate tan δ readings.
Mistake 3 – Ignoring test voltage level: For CVTs, test at rated primary voltage. Testing at lower voltages may not stress the full capacitor stack uniformly.
Mistake 4 – Not recording temperature: Instrument transformers are often tested in varying seasons. Without temperature correction, trending is meaningless.
Mistake 5 – Assuming identical units will have identical tan δ: Manufacturing variations cause legitimate differences. Trend each unit individually rather than comparing across units.
Instrument transformer failure does more than damage equipment – it compromises protection and metering. When marketing tan delta testers to utilities and industrial facilities, emphasize that reliable CTs and VTs are essential for differential protection, distance relaying, and revenue accuracy. Provide free instrument transformer testing templates and trending spreadsheets. Train your sales team to ask: When was the last time your CTs and VTs were insulation tested? Then demonstrate how your tan delta tester reveals hidden deterioration that could disable protection zones.
Instrument transformers – CTs and VTs – are critical but often neglected assets in high voltage substations. Tan delta testing provides a practical, sensitive, and non-destructive method for assessing their insulation condition without removal from service. By establishing baselines, trending measurements annually, applying proper temperature correction, and interpreting both dissipation factor and capacitance trends, substation owners can detect moisture ingress, internal arcing, and solid insulation deterioration before failure occurs. Implement a regular instrument transformer tan delta testing program – the cost is minimal compared to a bus fault or protection misoperation event.
Tan Delta Testing for Instrument Transformers: CT and VT Insulation Diagnostics for Protection and Metering Reliability
Tan Delta Testing for Generator and Motor Stator Windings: Diagnostics for Rotating Machine Reliability
Temperature and Humidity Correction Methods for Accurate Tan Delta Measurements in Field Environments
Tan Delta Tester vs. Other Insulation Diagnostic Methods: A Technical Comparison for HV Asset Owners