Proper interpretation of lightning impulse test results is critical for assessing equipment dielectric strength and compliance with IEC 60060 standards. This guide explains key analysis techniques for reliable evaluation of your high-voltage test outcomes.
Understand these fundamental waveform characteristics:
Peak Voltage (Up): Must be within ±3% of target value
Front Time (T1): 1.2μs ±30% tolerance
Time to Half Value (T2): 50μs ±20% tolerance
Overshoot: <5% of peak value per IEC 60060-1
Follow this systematic analysis approach:
Waveform Comparison: Overlay test and reference waveforms
Time Parameter Verification: Check T1 and T2 compliance
Peak Voltage Analysis: Verify within specified tolerance
Visual Inspection: Examine for partial discharge marks
| Abnormality | Potential Cause | Action Required |
|---|---|---|
| Waveform oscillation | Improper grounding | Check test setup |
| Reduced peak voltage | Insulation failure | Detailed insulation test |
| Increased front time | Test object capacitance | Adjust wave shaping |
Modern laboratories employ:
Frequency spectrum analysis of impulses
Time-frequency domain transformations
3D voltage distribution modeling
Automated defect classification algorithms
Comprehensive test reports should include:
Complete test circuit diagram
Measurement system calibration data
Environmental conditions during test
Waveform recordings with timestamps
Conclusion with acceptance criteria
Mastering these interpretation techniques ensures accurate assessment of your high-voltage equipment's lightning withstand capability. Proper analysis not only verifies compliance but also provides valuable insights into equipment condition and potential failure modes.
The Importance of Excitation Current Measurement in Transformer TTR Testing
Key Specifications to Evaluate When Purchasing a Transformer Turns Ratio Meter
Case Study: Detecting and Diagnosing Shorted Turns with a Transformer Turns Ratio Meter
How to Use TTR Test Results for Transformer Life Assessment and Failure Prediction